Error code
Remote controller:
7-segment display:
LED Green Red
Indoor
Outdoor
Content
–
343
–
E30
E30
Unmatch connection of
indoor and outdoor unit
Keeps flashing
Stays Off
Keeps flashing
1 time flash
1. Applicable model
5. Troubleshooting
KXE6 multi outdoor unit
Diagnosis Countermeasure
Is
the signal wire
connection between
indoorand outdoor units
correctly ?
YES
NO
Is
the voltage
between L1-N at terminal
block of indoor unit
220/240V?
NO
Is the
vo
ltage
between L1-N,
L2-N and L3-N for
3-phase model and L1-N for
1-phase model at terminal
brock of outdoor unit
220/240V?
YES
YES
NO
Correct signal wiring
Replace outdoor control
PCB
Disconnection of wire for
power line
→
Correct it
Replace indoor control
PCB
2. Error detection method
3
.
Condition of error displayed
4. Presumable cause
• Faulty indoor control PCB
• Faulty outdoor control PCB
Note:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT160KXE6 and is the answer not in the manual?

Mitsubishi Heavy Industries FDT160KXE6 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT160KXE6
CategoryAir Conditioner
LanguageEnglish

Related product manuals