42
-
'18 • SCM-T-251
Adapted to RoHS directive
Model
Item
FDUM50VF
Power source 1 Phase, 220
−
240V, 50Hz/220V, 60Hz
Operation data Cooling Heating
Nominal capacity (1) kW 5.0 5.8
Sound power level
dB(A)
60
Sound pressure level P-Hi : 37 Hi : 32 Me : 29 Lo : 26
Exterior dimensions
Height x Width x Depth
mm 280 × 750 × 635
Exterior appearance
(Munsell color)
—
Net weight kg 29
Heat exchanger Louver fin & inner grooved tubing
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 1
Motor <Starting method> W 100 < Direct line start >
Air flow (Standard) m
3
/min P-Hi : 13 Hi : 10 Me : 9 Lo : 8
Available external static pressure
Pa Standard:35 Max:100
Outside air intake Possible
Air filter, Q'ty Procure locally
Shock & vibration absorber Rubber sleeve(for fan motor)
Insulation (Noise & heat) Polyurethane form
Remote control Wired : RC-EX3, RC-E5, RCH-E3 (option) Wireless : RCN-KIT4-E2 (option)
Room temperature control Thermostat by electronics
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Installation data
Refrigerant piping size
mm
Liquid line: I/U
φ
6.35 (1/4")
Gas line:
φ
12.7 (1/2")
Connecting method Flare piping
Drain pump Built-in Drain pump
Drain Hose connectable with VP25
Insulation for piping Necessary (both Liquid & Gas lines)
IP number IPX0
Standard accessories Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
The pipe length is 7.5m.
Item
Operation
Indoor air temperature Outdoor air temperature
External static pressure
of indoor unit
Standards
DB WB DB WB
Cooling 27ËšC 19ËšC 35ËšC 24ËšC
35Pa ISO5151-T1
Heating 20ËšC
−
7ËšC 6ËšC
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation
these values are somewhat higher due to ambient temperature.
(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(5) Static pressure of option air filter "UM-FL1EF" is 5Pa initially.
(6) If wireless remote control is used, only 3-speed fan setting (Hi-Me-Lo) is availabe.
(6) Duct connected Low/Middle static pressure type (FDUM)
R
PJG000Z159

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM60ZM-S1 and is the answer not in the manual?

Mitsubishi Heavy Industries SCM60ZM-S1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM60ZM-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals