'17 • SRK-T-206
'09•SRK-DB-087D
Current cut
Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
Current safe stop
Overload operation, compressor
lock, overcharge
118.
SRK20, 25, 35 : 4.293Ω (U-V, V-W, U-W) or more at 20ºC
SRK45 : 1.104Ω (U-V, V-W, U-W) or more at 20ºC
SRK63 : 0.864Ω (U-V, V-W, U-W) or more at 20ºC
SRK71, 80 : 1.155Ω (U-V), 1.133Ω (V-W), 1.174Ω (U-W) or more at 20ºC