EasyManua.ls Logo

Mitsubishi FDK15KXZE1 - Page 100

Mitsubishi FDK15KXZE1
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
'17 • KX-T-264
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E16
Indoor DC fan motor anomaly
Keeps ashing
1-time ash
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
NO
YES
YES
YES
Does any
foreign material
intervene in rotational area
of fan propeller?
Is DC280V detected
between FDT : -, FDK : -
of fan motor connector
CNM?
Is it normalized?
Is the fuse F1 or F2 blown?
Does the fan
rotate smoothly when turned
by hand?
YES
NO
NO
NO
YES
NO
YES
Power source reset
Is DC15V
detected between connector
CNM FDT : -, FDK : -when
the fan motor on command
is released?
Is DC15V detected
between CNM FDT : -, FDK : -
when the connector is disconnected at the fan motor side
and the fan motor on command is
released?
NO
NO
YES
Remove foreign material.
Replace the fan motor.
Check power voltage.
Replace faulty fan motor
and power PCB.
Replace the indoor unit
control PCB.
Replace fan motor.
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor unit control PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
indoor fan motor
3 .
Condition of error displayed
When actual rotation speed of
indoor fan motor drops to lower
than 200min
-1
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
After 2-seconds, it starts
again automatically, but if this
error occurs 4 times within
60 minutes after the initial
detection.
4. Presumable cause
Defective indoor unit power
(control) PCB
Foreign material at rotational
area of fan propeller
Defective fan motor
Dust on control PCB
Blown fuse
External noise, surge
Note:
99