32
–
'17 • KX-T-264
ŷBefore installation
ŸSelection of installation location for the indoor unit
Installation-related items
Mounting plate
Tapping screw Insulation Strap
1 10 1 4
Attached to the backside of the indoor unit. For heat insulation, 50mm x 160mm For wire clampFor the mounting plate,
4mm (dia.) x 25mm (length)
Space for installation and service
UNIT: mm
INSTALLATION MANUAL FOR WALL-MOUNTED UNIT (FDK)
This manual is for the installation of an indoor unit.
For electrical wiring work (Indoor), refer to the electrical wiring work installation manual. For remote
controller installation, refer to the installation manual attached to a remote controller. For wireless kit
installation, refer to the installation manual attached to a wireless kit. For electrical wiring work
(Outdoor) and refrigerant pipe work installation for outdoor unit, refer to the installation manual
attached to an outdoor unit.
źInstallation of indoor unit
Over 65
Over 50 Over 100
ATTENTION
ȵSecure a working space for inspection and maintenance.
Datum hole
ATTENTION
ȵThis unit cannot be installed directly onto a wall surface. Regardless of the surface it is to be
installed onto, you should use the mounting plate supplied with the unit.
ȿȳ
Install it securely by spotting a structural member running underneath the wall (stud or the
like) and after ascertaining its levelness.
ȿȳThe levelness of the mounting plate should be adjusted with the four fixing screws fastened
temporarily.
ȿȳRotate the plate around the datum hole to achieve the levelness.
Installation of the mounting plate
Hints for making a hole on a wall
Haulage
ȿȳGive a descending grade of 5from the interior to the exterior.
Level positioning mark
Level guide (2 places)
B
Wall
Sleeve
Sealing plate
Indoor
65mm
Outdoor
Wall
Sleeve
Type 22
56
450
Type 71
450,610
UNIT: mm
Model
B Size
ATTENTION
ȵ
In carrying the unit into an installation site, carry it in the original
packaging to a point as close to the proposed installation site as
possible.
ȵWhen the unit needs to be unpacked during haulage due to a
compelling reason, wrap it with nylon slings or the like to prevent
possible damages.
Note: Do not hold the unit by the diffuser louver in carrying it.
ȵWhen the unit needs to be laid on a floor after unpacking, always lay
it with its front facing upward.
ŹPreparation before installation
Service space 50
50 50
25
53.5
450
Service space 100
Service spaceService space
44.5
44.5 65
8.5
4-12x18 oval hole
-5x17.5 oval hole
A
C
B
E
D
Installing plate
Indoor unit
Hole for public corporation
3 1
5
7
3
9
10
11
12
21
20
19
6
8
4
18
16
17
15
14
213
609
55
3
F
G
Front view for installing position and installing space
ȵ!Read the “SAFETY PRECAUTIONS” carefully first of all and then strictly follow it during the installation work
in order to protect yourself.
ȵ!The precautionary items mentioned below are distinguished into two levels, and .
: Wrong installation would cause serious consequences such as injuries or death.
: Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
ȵAfter completing the installation, do commissioning to confirm there are no abnormalities, and explain to the
customers about “SAFETY PRECAUTIONS”, correct operation method and maintenance method (air filter
cleaning, operation method and temperature setting method) with user’s manual of this unit.
Ask your customers to keep this installation manual together with the user’s manual. Also, ask them to hand
over the user’s manual to the new user when the owner is changed.
CAUTION
CAUTION
ȵInstallation should be performed by the specialist.
If you install the unit by yourself, it may lead to serious trouble such as water leakage, electric shock, fire, and injury due to overturn
of the unit.
ȵInstall the system correctly according to these installation manuals.
Improper installation may cause explosion, injury, water leakage, electric shock, and fire.
ȵConsider measurement not to exceed the limit of the density of refrigerant in the event of leakage especially
when it is installed in a small room.
Consult the specialist about the measure. If the density of refrigerant exceeds the limit in the event of the leakage, serious accidents
may occur due to lack of oxygen.
ȵUse the genuine accessories and the specified parts for installation.
If parts unspecified by our company are used it could cause water leakage, electric shock, fire, and injury due to overturn of the unit.
ȵVentilate the working area well in case the refrigerant leaks during installation.
If the refrigerant contacts the fire, toxic gas is produced.
ȵInstall the unit in a location that can hold heavy weight.
Improper installation may cause the unit to fall leading to accidents.
ȵInstall the unit properly in order to be able to withstand strong winds such as typhoons, and earthquakes.
Improper installation may cause the unit to fall leading to accidents.
ȵDo not mix air in to the cooling cycle on installation or removal of the air conditioner.
If air is mixed in, the pressure in the cooling cycle will rise abnormally and may cause explosion and injuries.
ȵBe sure to have the electrical wiring work done by qualified electrical installer, and use exclusive circuit.
Power source with insufficient capacity and improper work can cause electric shock and fire.
ȵUse specified wire for electrical wiring, fasten the wiring to the terminal securely, and hold the cable securely in
order not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
ȵArrange the electrical wires in the control box properly to prevent them from rising. Fit the lid of the services
panel property.
Improper fitting may cause abnormal heat and fire.
ȵCheck for refrigerant gas leakage after installation is completed.
If the refrigerant gas leaks into the house and comes in contact with a fan heater, a stove, or an oven, toxic gas is produced.
ȵUse the specified pipe, flare nut, and tools for R410A.
Using existing parts (R22) could cause the unit failure and serious accident due to explosion of the cooling cycle.
ȵTighten the flare nut according to the specified method by with torque wrench.
If the flare nut were tightened with excess torque, it could cause burst and refrigerant leakage after a long period.
ȵMake sure there is no dust or clogging on both the plug and the socket nor loose connection of the socket
before plugging, and plug in securely to the end of the blade.
Accumulation of dust, clogging on the socket or plug, or loose installation of the socket could cause electric shock and fire. Replace
the socket if it is loose.
ȵConnect the pipes for refrigeration circuit securely in installation work before compressor is operated.
If the compressor is operated when the service valve is open without connecting the pipe, it could cause explosion and injuries due
to abnormal high pressure in the system.
ȵStop the compressor before removing the pipe on pump down work.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit
and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle.
ȵUse the genuine optional parts. And installation should be performed by a specialist.
If you install the unit by yourself, it could cause water leakage, electric shock and fire.
ȵDo not repair by yourself. And consult with the dealer about repair.
Improper repair may cause water leakage, electric shock or fire.
ȵConsult the dealer or a specialist about removal of the air conditioner.
Improper installation may cause water leakage, electric shock or fire.
ȵTurn off the power source during servicing or inspection work.
If the power is supplied during servicing or inspection work, it could cause electric shock and injury by the operating fan.
ȵDo not run the unit when the panel or protection guard are taken off.
Touching the rotating equipment, hot surface, or high voltage section could cause an injury to be caught in the machine, to get
burned, or electric shock.
ȵShut off the power before electrical wiring work.
It could cause electric shock, unit failure and improper running.
ȵ!Perform earth wiring surely.
Do not connect the earth wiring to the gas pipe, water pipe, lightning rod and telephone earth wiring. Improper earth could
cause unit failure and electric shock due to a short circuit.
ȵ!Use the circuit breaker of correct capacity.
Using the incorrect capacity one could cause the system failure and fire.
ȵ!Do not use any materials other than a fuse of correct capacity where a fuse should be used.
Connecting the circuit by wire or copper wire could cause unit failure and fire.
ȵ!Do not install the indoor unit near the location where there is possibility of flammable gas leakages.
If the gas leaks and gathers around the unit, it could cause fire.
ȵ!Do not install and use the unit where corrosive gas (such as sulfurous acid gas etc.) or flammable gas
(such as thinner, petroleum etc.) may be generated or accumulated, or volatile flammable substances
are handled.
It could cause the corrosion of heat exchanger, breakage of plastic parts etc. And inflammable gas could cause fire.
ȵ!Do not use the indoor unit at the place where water splashes such as laundry.
Indoor unit is not waterproof. It could cause electric shock and fire.
ȵ Do not use the indoor unit for a special purpose such as food storage, cooling for precision
instrument, preservation of animals, plants, and a work of art.
It could cause the damage of the items.
ȵ Do not install nor use the system near equipments which generate electromagnetic wave or high
harmonics.
Equipments like inverter equipment, private power generator, high-frequency medical equipment, or telecommunication
equipment might influence the air conditioner and cause a malfunction and breakdown. Or the air conditioner might
influence medical equipments or telecommunication equipments, and obstruct their medical activity or cause jamming.
ȵ Do not install the remote controller at the direct sunlight.
It could cause breakdown or deformation of the remote controller.
ȵ Do not install the indoor unit at the place listed below.
· Places where flammable gas could leak.
· Places where carbon fiber, metal powder or any powder is floated.
· Place where the substances which affect the air conditioner are generated such as sulfide gas, chloride gas, acid or
alkali.
· Places exposed to oil mist or steam directly.
· On vehicles and ships
· Places where machinery which generates high harmonics is used.
· Places where cosmetics or special sprays are frequently used.
· Highly salted area such as beach.
· Heavy snow area
· Places where the system is affected by smoke from a chimney.
· Altitude over 1000m
ȵ Do not put any valuables which will break down by getting wet under the air conditioner.
Condensation could drop when the relative humidity is higher than 80% or drain pipe is clogged, and it damages user’s
belongings.
ȵ Do not use the base frame for the outdoor unit which is corroded or damaged after a long period of
use.
It could cause the unit falling down and injury.
ȵ Pay attention not to damage the drain pan by weld sputter when brazing work is done near the unit.
If sputter entered into the unit during brazing work, it could cause damage (pinhole) of drain pan and leakage of water. To
avoid damaging, keep the indoor unit packed or cover the indoor unit.
ȵ Install the drain pipe to drain the water surely according to the installation manual.
Improper connection of the drain pipe may cause dropping water into room and damaging user’s belongings.
ȵ Do not put the drain pipe directly into the ditch where toxic gas such as sulfide gas is generated.
Toxic gas would flow into the room and it would cause serious damage to user’s health and safety.
ȵ Do not share the drain pipe for indoor unit and GHP (Gas Heat Pump system) outdoor unit.
Toxic exhaust gas would flow into room and it might cause serious damage (some poisoning or deficiency of oxygen) to
user’s health and safety.
ȵ For drain pipe installation, be sure to make descending slope of greater than 1/100, not to make traps,
and not to make air-bleeding.
Check if the drainage is correctly done during commissioning and ensure the space for inspection and maintenance.
ȵ Ensure the insulation on the pipes for refrigeration circuit so as not to condense water.
Incomplete insulation could cause condensation and it would wet ceiling, floor, and any other valuables.
ȵ Do not install the outdoor unit where is likely to be a nest for insects and small animals.
Insects and small animals could come into the electronic components and cause breakdown and fire. Instruct the user to
keep the surroundings clean.
ȵ Pay extra attention, carrying the unit by hand.
Carry the unit with 2 people if it is heavier than 20kg. Do not use the plastic straps but the grabbing place, moving the unit
by hand. Use protective gloves in order to avoid injury by the aluminum fin.
ȵ Make sure to dispose of the packaging material.
Leaving the materials may cause injury as metals like nail and woods are used in the package.
ȵ Do not operate the system without the air filter.
It may cause the breakdown of the system due to clogging of the heat exchanger.
ȵ Do not touch any button with wet hands
It could cause electric shock.
ȵ Do not touch the refrigerant piping with bare hands when in operation.
The pipe during operation would become very hot or cold according to the operating condition, and it could cause a burn
or frostbite.
ȵ
Do not clean up the air conditioner with water.
It could cause electric shock.
ȵ
Do not turn off the power source immediately after stopping the operation.
Be sure to wait for more than 5 minutes. Otherwise it could cause water leakage or breakdown.
ȵ
Do not control the operation with the circuit breaker.
It could cause fire or water leakage. In addition, the fan may start operation unexpectedly and it may cause injury.
WARNING
CAUTION
ŷ!Select the suitable areas to install the unit under approval of the user.
ȿAreas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user
to use a circulator if the ceiling height is over 3m to avoid warm air being accumulated on
the ceiling.
Areas where there is enough space to install and service.
Areas where it can be drained properly. Areas where drain pipe descending slope can be
taken.
Areas where there is no obstruction of airflow on both air return grille and air supply port.
Areas where fire alarm will not be accidentally activated by the air conditioner.
Areas where the supply air does not short-circuit.
Areas where it is not influenced by draft air.
Areas not exposed to direct sunlight.
Areas where dew point is lower than around 23°C and relative humidity is lower than 80%.
This indoor unit is tested under the condition of JIS (Japan Industrial Standard) high humid-
ity condition and confirmed there is no problem. However, there is some risk of condensa-
tion drop if the air conditioner is operated under the severer condition than mentioned
above.
Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.)
Areas where any items which will be damaged by getting wet are not placed such as food,
table wares, server, or medical equipment under the unit.
Areas where there is no influence by the heat which cookware generates.
Areas where not exposed to oil mist, powder and/or steam directly such as above fryer.
Areas where lighting device such as fluorescent light or incandescent light doesn’t affect the
operation.
(A beam from lighting device sometimes affects the infrared receiver for the wireless remote
controller and the air conditioner might not work properly.)
ŸCheck if the place where the air conditioner is installed can hold the weight of the unit. If it is
not able to hold, reinforce the structure with boards and beams strong enough to hold it. If the
strength is not enough, it could cause injury due to unit falling.
UNIT: mm
ȵInstall correctly according to the installation manual.
ȵConfirm the following points:
ȿȳUnit type/Power supply specification ȳPipes/Wires/Small parts ȳAccessory items
Symbol
A
B
C
D
E
F
G
Gas piping
Liquid piping
Wall pulling hole for right rear piping
Wall pulling hole for left rear piping
Drain piping
Outlet for wiring
Outlet for piping
Symbol Type 22 - 56 Type 71
693
284.2
73.5
-
-
-
207.5
182.5
63.5
533.5
603.5
515
5.3
-
220.5
47.5
-
-
886
301.8
106
610
269
219
349
299
77
633.5
703.5
772
7.7
43
221.5
49.5
259 248
225
46
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
0 25
19
2 6
20
21
18
PHA012D039
4"'&5:13&$"65*0/4
8"3/*/(
$"65*0/
● 3FBEUIFi4"'&5:13&$"65*0/4wDBSFGVMMZmSTUPGBMMBOEUIFOTUSJDUMZGPMMPXJUEVSJOHUIFJOTUBMMBUJPOXPSL
JOPSEFSUPQSPUFDUZPVSTFMG
● 5IFQSFDBVUJPOBSZJUFNTNFOUJPOFECFMPXBSFEJTUJOHVJTIFEJOUPUXPMFWFMTBOE
8SPOHJOTUBMMBUJPOXPVMEDBVTFTFSJPVTDPOTFRVFODFTTVDIBTJOKVSJFTPSEFBUI
8SPOHJOTUBMMBUJPONJHIUDBVTFTFSJPVTDPOTFRVFODFTEFQFOEJOHPODJSDVNTUBODFT
#PUINFOUJPOTUIFJNQPSUBOUJUFNTUPQSPUFDUZPVSIFBMUIBOETBGFUZTPTUSJDUMZGPMMPXUIFNCZBOZNFBOT
●5IFNFBOJOHTPGi.BSLTwVTFEIFSFBSFBTTIPXOBTGPMMPXT
●
"GUFSDPNQMFUJOHUIFJOTUBMMBUJPOEPDPNNJTTJPOJOHUPDPOmSNUIFSFBSFOPBCOPSNBMJUJFTBOEFYQMBJOUPUIF
DVTUPNFSTBCPVUi4"'&5:13&$"65*0/4wDPSSFDUPQFSBUJPONFUIPEBOENBJOUFOBODFNFUIPEBJSmMUFS
DMFBOJOHPQFSBUJPONFUIPEBOEUFNQFSBUVSFTFUUJOHNFUIPEXJUIVTFSTNBOVBMPGUIJTVOJU
"TLZPVSDVTUPNFSTUPLFFQUIJTJOTUBMMBUJPONBOVBMUPHFUIFSXJUIUIFVTFSTNBOVBM"MTPBTLUIFNUPIBOE
PWFSUIFVTFSTNBOVBMUPUIFOFXVTFSXIFOUIFPXOFSJTDIBOHFE
$"65*0/
/FWFSEPJUVOEFSBOZDJSDVNTUBODFT
$"65*0/
●*OTUBMMBUJPOTIPVMECFQFSGPSNFECZUIFTQFDJBMJTU
*GZPVJOTUBMMUIFVOJUCZZPVSTFMGJUNBZMFBEUPTFSJPVTUSPVCMFTVDIBTXBUFSMFBLBHFFMFDUSJDTIPDLmSFBOEJOKVSZEVFUPPWFSUVSOPGUIFVOJU
●*OTUBMMUIFTZTUFNDPSSFDUMZBDDPSEJOHUPUIFTFJOTUBMMBUJPONBOVBMT
*NQSPQFSJOTUBMMBUJPONBZDBVTFFYQMPTJPOJOKVSZXBUFSMFBLBHFFMFDUSJDTIPDLBOEmSF
●8IFOJOTUBMMJOHJOTNBMMSPPNTUBLFQSFWFOUJPONFBTVSFTOPUUPFYDFFEUIFEFOTJUZMJNJUPGSFGSJHFSBOUJOUIF
FWFOUPGMFBLBHFSFGFSSFECZUIFGPSNVMBBDDPSEBODF XJUI *40
*G UIF EFOTJUZ PGSFGSJHFSBOUFYDFFETUIFMJNJUQMFBTFDPOTVMUUIFEFBMFSBOEJOTUBMMUIFWFOUJMBUJPOTZTUFNPUIFSXJTFMBDLPG
PYZHFODBOPDDVSXIJDIDBODBVTFTFSJPVTBDDJEFOUT
●6TFUIFHFOVJOFBDDFTTPSJFTBOEUIFTQFDJmFEQBSUTGPSJOTUBMMBUJPO
*GQBSUTVOTQFDJmFECZPVSDPNQBOZBSFVTFEJUDPVMEDBVTFXBUFSMFBLBHFFMFDUSJDTIPDLmSFBOEJOKVSZEVFUPPWFSUVSOPGUIFVOJU
●7FOUJMBUFUIFXPSLJOHBSFBXFMMJODBTFUIFSFGSJHFSBOUMFBLTEVSJOHJOTUBMMBUJPO
*GUIFSFGSJHFSBOUDPOUBDUTUIFmSFUPYJDHBTJTQSPEVDFE
●*OTUBMMUIFVOJUJOBMPDBUJPOUIBUDBOIPMEIFBWZXFJHIU
*NQSPQFSJOTUBMMBUJPONBZDBVTFUIFVOJUUPGBMMMFBEJOHUPBDDJEFOUT
●*OTUBMMUIFVOJUQSPQFSMZJOPSEFSUPCFBCMFUPXJUITUBOETUSPOHXJOETTVDIBTUZQIPPOTBOEFBSUIRVBLFT
*NQSPQFSJOTUBMMBUJPONBZDBVTFUIFVOJUUPGBMMMFBEJOHUPBDDJEFOUT
●%POPUNJYBJSJOUPUIFDPPMJOHDZDMFPOJOTUBMMBUJPOPSSFNPWBMPGUIFBJSDPOEJUJPOFS
*GBJSJTNJYFEJOUIFQSFTTVSFJOUIFDPPMJOHDZDMFXJMMSJTFBCOPSNBMMZBOENBZDBVTFFYQMPTJPOBOEJOKVSJFT
●#FTVSFUPIBWFUIFFMFDUSJDBMXJSJOHXPSLEPOFCZRVBMJmFEFMFDUSJDBMJOTUBMMFSBOEVTFFYDMVTJWFDJSDVJU
1PXFSTPVSDFXJUIJOTVGmDJFOUDBQBDJUZBOEJNQSPQFSXPSLDBODBVTFFMFDUSJDTIPDLBOEmSF
●
6TFTQFDJmFEXJSFGPSFMFDUSJDBMXJSJOHGBTUFOUIFXJSJOHUPUIFUFSNJOBMTFDVSFMZBOEIPMEUIFDBCMFTFDVSFMZJO
PSEFSOPUUPBQQMZVOFYQFDUFETUSFTTPOUIFUFSNJOBM
-PPTFDPOOFDUJPOTPSIPMEDPVMESFTVMUJOBCOPSNBMIFBUHFOFSBUJPOPSmSF
●"SSBOHFUIFFMFDUSJDBMXJSFTJOUIFDPOUSPMCPYQSPQFSMZUPQSFWFOUUIFNGSPNSJTJOH'JUUIFMJEPGUIFTFSWJDFT
QBOFMQSPQFSUZ
*NQSPQFSmUUJOHNBZDBVTFBCOPSNBMIFBUBOEmSF
●$IFDLGPSSFGSJHFSBOUHBTMFBLBHFBGUFSJOTUBMMBUJPOJTDPNQMFUFE
*GUIFSFGSJHFSBOUHBTMFBLTJOUPUIFIPVTFBOEDPNFTJODPOUBDUXJUIBGBOIFBUFSBTUPWFPSBOPWFOUPYJDHBTJTQSPEVDFE
●6TFUIFTQFDJmFEQJQFnBSFOVUBOEUPPMTGPS3"
6TJOHFYJTUJOHQBSUT3DPVMEDBVTFUIFVOJUGBJMVSFBOETFSJPVTBDDJEFOUEVFUPFYQMPTJPOPGUIFDPPMJOHDZDMF
●5JHIUFOUIFnBSFOVUBDDPSEJOHUPUIFTQFDJmFENFUIPECZXJUIUPSRVFXSFODI
*GUIFnBSFOVUXFSFUJHIUFOFEXJUIFYDFTTUPSRVFJUDPVMEDBVTFCVSTUBOESFGSJHFSBOUMFBLBHFBGUFSBMPOHQFSJPE
●
%POPUQVUUIFESBJOBHFQJQFEJSFDUMZJOUPESBJOBHFDIBOOFMTXIFSFQPJTPOPVTHBTFTTVDIBTTVMmEFHBTDBOPDDVS
1PJTPOPVTHBTFTXJMMnPXJOUPUIFSPPNUISPVHIESBJOBHFQJQFBOETFSJPVTMZBGGFDUUIFVTFShTIFBMUIBOETBGFUZ5IJTDBOBMTP
DBVTFUIFDPSSPTJPOPGUIFJOEPPSVOJUBOEBSFTVMUBOUVOJUGBJMVSFPSSFGSJHFSBOUMFBL
●$POOFDUUIFQJQFTGPSSFGSJHFSBUJPODJSDVJUTFDVSFMZJOJOTUBMMBUJPOXPSLCFGPSFDPNQSFTTPSJTPQFSBUFE
*GUIFDPNQSFTTPSJTPQFSBUFEXIFOUIFTFSWJDFWBMWFJTPQFOXJUIPVUDPOOFDUJOHUIFQJQFJUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFTEVF
UPBCOPSNBMIJHIQSFTTVSFJOUIFTZTUFN
●4UPQUIFDPNQSFTTPSCFGPSFSFNPWJOHUIFQJQFBGUFSTIVUUJOHUIFTFSWJDFWBMWFPOQVNQEPXOXPSL
*GUIFQJQFJTSFNPWFEXIFOUIFDPNQSFTTPSJTJOPQFSBUJPOXJUIUIFTFSWJDFWBMWFPQFOBJSXPVMECFNJYFEJOUIFSFGSJHFSBUJPODJSDVJU
BOEJUDPVMEDBVTFFYQMPTJPOBOEJOKVSJFTEVFUPBCOPSNBMIJHIQSFTTVSFJOUIFDPPMJOHDZDMF
●0OMZVTFQSFTDSJCFEPQUJPOBMQBSUT5IFJOTUBMMBUJPONVTUCFDBSSJFEPVUCZUIFRVBMJmFEJOTUBMMFS
*GZPVJOTUBMMUIFTZTUFNCZZPVSTFMGJUDBODBVTFTFSJPVTUSPVCMFTVDIBTXBUFSMFBLTFMFDUSJDTIPDLTmSF
●%POPUSFQBJSCZZPVSTFMG"OEDPOTVMUXJUIUIFEFBMFSBCPVUSFQBJS
*NQSPQFSSFQBJSNBZDBVTFXBUFSMFBLBHFFMFDUSJDTIPDLPSmSF
●$POTVMUUIFEFBMFSPSBTQFDJBMJTUBCPVUSFNPWBMPGUIFBJSDPOEJUJPOFS
*NQSPQFSJOTUBMMBUJPONBZDBVTFXBUFSMFBLBHFFMFDUSJDTIPDLPSmSF
●5VSOPGGUIFQPXFSTPVSDFEVSJOHTFSWJDJOHPSJOTQFDUJPOXPSL
*GUIFQPXFSJTTVQQMJFEEVSJOHTFSWJDJOHPSJOTQFDUJPOXPSLJUDPVMEDBVTFFMFDUSJDTIPDLBOEJOKVSZCZUIFPQFSBUJOHGBO
●%POPUSVOUIFVOJUXIFOUIFQBOFMPSQSPUFDUJPOHVBSEBSFUBLFOPGG
5PVDIJOHUIFSPUBUJOHFRVJQNFOUIPUTVSGBDFPSIJHIWPMUBHFTFDUJPODPVMEDBVTFBOJOKVSZUPCFDBVHIUJOUIFNBDIJOFUPHFU
CVSOFEPSFMFDUSJDTIPDL
●4IVUPGGUIFQPXFSCFGPSFFMFDUSJDBMXJSJOHXPSL
*UDPVMEDBVTFFMFDUSJDTIPDLVOJUGBJMVSFBOEJNQSPQFSSVOOJOH
● 1FSGPSNFBSUIXJSJOHTVSFMZ
%POPUDPOOFDUUIFFBSUIXJSJOHUPUIFHBTQJQFXBUFSQJQFMJHIUOJOHSPEBOEUFMFQIPOFFBSUIXJSJOH*NQSPQFSFBSUIDPVME
DBVTFVOJUGBJMVSFBOEFMFDUSJDTIPDLEVFUPBTIPSUDJSDVJU
● &BSUIMFBLBHFCSFBLFSNVTUCFJOTUBMMFE
*GUIFFBSUIMFBLBHFCSFBLFSJTOPUJOTUBMMFEJUDBODBVTFFMFDUSJDTIPDLT
● 6TFUIFDJSDVJUCSFBLFSPGDPSSFDUDBQBDJUZ$JSDVJUCSFBLFSTIPVMECFUIFPOFUIBUEJTDPOOFDUBMM
QPMFTVOEFSPWFSDVSSFOU
6TJOHUIFJODPSSFDUPOFDPVMEDBVTFUIFTZTUFNGBJMVSFBOEmSF
● %POPUVTFBOZNBUFSJBMTPUIFSUIBOBGVTFPGDPSSFDUDBQBDJUZXIFSFBGVTFTIPVMECFVTFE
$POOFDUJOHUIFDJSDVJUCZXJSFPSDPQQFSXJSFDPVMEDBVTFVOJUGBJMVSFBOEmSF
● %POPUJOTUBMMUIFJOEPPSVOJUOFBSUIFMPDBUJPOXIFSFUIFSFJTQPTTJCJMJUZPGnBNNBCMFHBTMFBLBHFT
*GUIFHBTMFBLTBOEHBUIFSTBSPVOEUIFVOJUJUDPVMEDBVTFmSF
●
%POPUJOTUBMMBOEVTFUIFVOJUXIFSFDPSSPTJWFHBTTVDIBTTVMGVSPVTBDJEHBTFUDPSnBNNBCMFHBTTVDI
BTUIJOOFSQFUSPMFVNFUDNBZCFHFOFSBUFEPSBDDVNVMBUFEPSWPMBUJMFnBNNBCMFTVCTUBODFTBSFIBOEMFE
*UDPVMEDBVTFUIFDPSSPTJPOPGIFBUFYDIBOHFSCSFBLBHFPGQMBTUJDQBSUTFUD"OEJOnBNNBCMFHBTDPVMEDBVTFmSF
● 4FDVSFBTQBDFGPSJOTUBMMBUJPOJOTQFDUJPOBOENBJOUFOBODFTQFDJmFEJOUIFNBOVBM
*OTVGmDJFOUTQBDFDBOSFTVMUJOBDDJEFOUTVDIBTQFSTPOBMJOKVSZEVFUPGBMMJOHGSPNUIFJOTUBMMBUJPOQMBDF
● %POPUVTFUIFJOEPPSVOJUBUUIFQMBDFXIFSFXBUFSTQMBTIFTTVDIBTMBVOESZ
*OEPPSVOJUJTOPUXBUFSQSPPG*UDPVMEDBVTFFMFDUSJDTIPDLBOEmSF
● %POPUVTFUIFJOEPPSVOJUGPSBTQFDJBMQVSQPTFTVDIBTGPPETUPSBHFDPPMJOHGPSQSFDJTJPO
JOTUSVNFOUQSFTFSWBUJPOPGBOJNBMTQMBOUTBOEBXPSLPGBSU
*UDPVMEDBVTFUIFEBNBHFPGUIFJUFNT
●
%POPUJOTUBMMOPSVTFUIFTZTUFNOFBSFRVJQNFOUTXIJDIHFOFSBUFFMFDUSPNBHOFUJDXBWFPSIJHIIBSNPOJDT
&RVJQNFOUTMJLFJOWFSUFSFRVJQNFOUQSJWBUFQPXFSHFOFSBUPSIJHIGSFRVFODZNFEJDBMFRVJQNFOUPSUFMFDPNNVOJDBUJPO
FRVJQNFOUNJHIUJOnVFODFUIFBJSDPOEJUJPOFSBOEDBVTFBNBMGVODUJPOBOECSFBLEPXO0SUIFBJSDPOEJUJPOFSNJHIU
JOnVFODFNFEJDBMFRVJQNFOUTPSUFMFDPNNVOJDBUJPOFRVJQNFOUTBOEPCTUSVDUUIFJSNFEJDBMBDUJWJUZPSDBVTFKBNNJOH
● %POPUJOTUBMMUIFSFNPUFDPOUSPMMFSBUUIFEJSFDUTVOMJHIU
*UDPVMEDBVTFCSFBLEPXOPSEFGPSNBUJPOPGUIFSFNPUFDPOUSPMMFS
● %POPUJOTUBMMUIFJOEPPSVOJUBUUIFQMBDFMJTUFECFMPX
r 1MBDFTXIFSFnBNNBCMFHBTDPVMEMFBL
r 1MBDFTXIFSFDBSCPOmCFSNFUBMQPXEFSPSBOZQPXEFSJTnPBUFE
r
1MBDFXIFSFUIFTVCTUBODFTXIJDIBGGFDUUIFBJSDPOEJUJPOFSBSFHFOFSBUFE
TVDIBTTVMmEFHBTDIMPSJEFHBTBDJEBMLBMJPSBNNPOJDBUNPTQIFSFT
r 1MBDFTFYQPTFEUPPJMNJTUPSTUFBNEJSFDUMZ
r 0OWFIJDMFTBOETIJQT
r 1MBDFTXIFSFNBDIJOFSZXIJDIHFOFSBUFTIJHIIBSNPOJDTJTVTFE
● %POPUJOTUBMMUIFJOEPPSVOJUJOUIFMPDBUJPOTMJTUFECFMPX#FTVSFUPJOTUBMMUIFJOEPPSVOJU
BDDPSEJOHUPUIFJOTUBMMBUJPONBOVBMGPSFBDINPEFMCFDBVTFFBDIJOEPPSVOJUIBTFBDIMJNJUBUJPO
r -PDBUJPOTXJUIBOZPCTUBDMFTXIJDIDBOQSFWFOUJOMFUBOEPVUMFUBJSPGUIFVOJU
r -PDBUJPOTXIFSFWJCSBUJPODBOCFBNQMJmFEEVFUPJOTVGmDJFOUTUSFOHUIPGTUSVDUVSF
r -PDBUJPOTXIFSFUIFJOGSBSFESFDFJWFSJTFYQPTFEUPUIFEJSFDUTVOMJHIUPSUIFTUSPOHMJHIUCFBNJODBTFPGUIF
JOGSBSFETQFDJmDBUJPOVOJU
r -PDBUJPOTXIFSFBOFRVJQNFOUBGGFDUFECZIJHIIBSNPOJDTJTQMBDFE57TFUPSSBEJPSFDFJWFSJTQMBDFEXJUIJON
r -PDBUJPOTXIFSFESBJOBHFDBOOPUSVOPGGTBGFMZ
*UDBOBGGFDUQFSGPSNBODFPSGVODUJPOBOEFUD
● %POPUQVUBOZWBMVBCMFTXIJDIXJMMCSFBLEPXOCZHFUUJOHXFUVOEFSUIFBJSDPOEJUJPOFS
$POEFOTBUJPODPVMEESPQXIFOUIFSFMBUJWFIVNJEJUZJTIJHIFSUIBOPSESBJOQJQFJTDMPHHFEBOEJUEBNBHFTVTFSTCFMPOHJOHT
●
%POPUVTFUIFCBTFGSBNFGPSUIFPVUEPPSVOJUXIJDIJTDPSSPEFEPSEBNBHFEBGUFSBMPOHQFSJPEPGVTF
*UDPVMEDBVTFUIFVOJUGBMMJOHEPXOBOEJOKVSZ
● 1BZBUUFOUJPOOPUUPEBNBHFUIFESBJOQBOCZXFMETQVUUFSXIFOCSB[JOHXPSLJTEPOFOFBSUIFVOJU
*GTQVUUFSFOUFSFEJOUPUIFVOJUEVSJOHCSB[JOHXPSLJUDPVMEDBVTFEBNBHFQJOIPMFPGESBJOQBOBOEMFBLBHFPGXBUFS
5PBWPJEEBNBHJOHLFFQUIFJOEPPSVOJUQBDLFEPSDPWFSUIFJOEPPSVOJU
● *OTUBMMUIFESBJOQJQFUPESBJOUIFXBUFSTVSFMZBDDPSEJOHUPUIFJOTUBMMBUJPONBOVBM
*NQSPQFSDPOOFDUJPOPGUIFESBJOQJQFNBZDBVTFESPQQJOHXBUFSJOUPSPPNBOEEBNBHJOHVTFSTCFMPOHJOHT
● %POPUTIBSFUIFESBJOQJQFGPSJOEPPSVOJUBOE()1(BT)FBU1VNQTZTUFNPVUEPPSVOJU
5PYJDFYIBVTUHBTXPVMEnPXJOUPSPPNBOEJUNJHIUDBVTFTFSJPVTEBNBHFTPNFQPJTPOJOHPSEFmDJFODZPGPYZHFOUP
VTFSTIFBMUIBOETBGFUZ
●
#FTVSFUPQFSGPSNBJSUJHIUOFTTUFTUCZQSFTTVSJ[JOHXJUIOJUSPHFOHBTBGUFSDPNQMFUFESFGSJHFSBOUQJQJOHXPSL
*GUIFEFOTJUZPGSFGSJHFSBOUFYDFFETUIFMJNJUJOUIFFWFOUPGSFGSJHFSBOUMFBLBHFJOUIFTNBMMSPPNMBDLPGPYZHFODBO
PDDVSXIJDIDBODBVTFTFSJPVTBDDJEFOUT
●
'PSESBJOQJQFJOTUBMMBUJPOCFTVSFUPNBLFEFTDFOEJOHTMPQFPGHSFBUFSUIBOOPUUPNBLFUSBQT
BOEOPUUPNBLFBJSCMFFEJOH
$IFDLJGUIFESBJOBHFJTDPSSFDUMZEPOFEVSJOHDPNNJTTJPOJOHBOEFOTVSFUIFTQBDFGPSJOTQFDUJPOBOENBJOUFOBODF
● &OTVSFUIFJOTVMBUJPOPOUIFQJQFTGPSSFGSJHFSBUJPODJSDVJUTPBTOPUUPDPOEFOTFXBUFS
*ODPNQMFUFJOTVMBUJPODPVMEDBVTFDPOEFOTBUJPOBOEJUXPVMEXFUDFJMJOHnPPSBOEBOZPUIFSWBMVBCMFT
● %POPUJOTUBMMUIFPVUEPPSVOJUXIFSFJTMJLFMZUPCFBOFTUGPSJOTFDUTBOETNBMMBOJNBMT
*OTFDUTBOETNBMMBOJNBMTDPVMEDPNFJOUPUIFFMFDUSPOJDDPNQPOFOUTBOEDBVTFCSFBLEPXOBOEmSF*OTUSVDUUIFVTFSUP
LFFQUIFTVSSPVOEJOHTDMFBO
● 1BZFYUSBBUUFOUJPODBSSZJOHUIFVOJUCZIBOE
$BSSZUIFVOJUXJUIQFPQMFJGJUJTIFBWJFSUIBOLH%POPUVTFUIFQMBTUJDTUSBQTCVUUIFHSBCCJOHQMBDFNPWJOHUIFVOJU
CZIBOE6TFQSPUFDUJWFHMPWFTJOPSEFSUPBWPJEJOKVSZCZUIFBMVNJOVNmO
● .BLFTVSFUPEJTQPTFPGUIFQBDLBHJOHNBUFSJBM
-FBWJOHUIFNBUFSJBMTNBZDBVTFJOKVSZBTNFUBMTMJLFOBJMBOEXPPETBSFVTFEJOUIFQBDLBHF
● %POPUPQFSBUFUIFTZTUFNXJUIPVUUIFBJSmMUFS
*UNBZDBVTFUIFCSFBLEPXOPGUIFTZTUFNEVFUPDMPHHJOHPGUIFIFBUFYDIBOHFS
● %POPUUPVDIBOZCVUUPOXJUIXFUIBOET
*UDPVMEDBVTFFMFDUSJDTIPDL
● %POPUUPVDIUIFSFGSJHFSBOUQJQJOHXJUICBSFIBOETXIFOJOPQFSBUJPO
5IFQJQFEVSJOHPQFSBUJPOXPVMECFDPNFWFSZIPUPSDPMEBDDPSEJOHUPUIFPQFSBUJOHDPOEJUJPOBOEJUDPVMEDBVTFBCVSOPSGSPTUCJUF
●
%POPUDMFBOVQUIFBJSDPOEJUJPOFSXJUIXBUFS
*UDPVMEDBVTFFMFDUSJDTIPDL
●
%POPUUVSOPGGUIFQPXFSTPVSDFJNNFEJBUFMZBGUFSTUPQQJOHUIFPQFSBUJPO
#FTVSFUPXBJUGPSNPSFUIBONJOVUFT0UIFSXJTFJUDPVMEDBVTFXBUFSMFBLBHFPSCSFBLEPXO
●
%POPUDPOUSPMUIFPQFSBUJPOXJUIUIFDJSDVJUCSFBLFS
*UDPVMEDBVTFmSFPSXBUFSMFBLBHF*OBEEJUJPOUIFGBONBZTUBSUPQFSBUJPOVOFYQFDUFEMZBOEJUNBZDBVTFJOKVSZ
"MXBZTEPJUBDDPSEJOHUPUIFJOTUSVDUJPO
r 1MBDFTXIFSFDPTNFUJDTPSTQFDJBMTQSBZTBSF
GSFRVFOUMZVTFE
r )JHIMZTBMUFEBSFBTVDIBTCFBDI
r )FBWZTOPXBSFB
r 1MBDFTXIFSFUIFTZTUFNJTBGGFDUFECZ
TNPLFGSPNBDIJNOFZ
r "MUJUVEFPWFSN
SAFETY PRECAUTIONS
WARNING
CAUTION
●
Read the “SAFETY PRECAUTIONS” carefully first of all and then strictly follow it during the installation work
in order to protect yourself.
●
The precautionary items mentioned below are distinguished into two levels, and .
: Wrong installation would cause serious consequences such as injuries or death.
: Wrong installation might cause serious consequences depending on circumstances.
Both mentions the important items to protect your health and safety so strictly follow them by any means.
●
The meanings of “Marks” used here are as shown as follows:
●
After completing the installation, do commissioning to confirm there are no abnormalities, and explain to the
customers about “SAFETY PRECAUTIONS”, correct operation method and maintenance method (air filter
cleaning, operation method and temperature setting method) with user’s manual of this unit.
Ask your customers to keep this installation manual together with the user’s manual. Also, ask them to hand
over the user’s manual to the new user when the owner is changed.
CAUTION
Never do it under any circumstances.
CAUTION
●
Installation should be performed by the specialist.
If you install the unit by yourself, it may lead to serious trouble such as water leakage, electric shock, fire, and injury due to overturn of the unit.
●
Install the system correctly according to these installation manuals.
Improper installation may cause explosion, injury, water leakage, electric shock, and fire.
●
When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant in the
event of leakage, referred by the formula (accordance with ISO5149).
If the density of refrigerant exceeds the limit, please consult the dealer and install the ventilation system, otherwise lack of
oxygen can occur, which can cause serious accidents.
●
Use the genuine accessories and the specified parts for installation.
If parts unspecified by our company are used it could cause water leakage, electric shock, fire, and injury due to overturn of the unit.
●
Ventilate the working area well in case the refrigerant leaks during installation.
If the refrigerant contacts the fire, toxic gas is produced.
●
Install the unit in a location that can hold heavy weight.
Improper installation may cause the unit to fall leading to accidents.
●
Install the unit properly in order to be able to withstand strong winds such as typhoons, and earthquakes.
Improper installation may cause the unit to fall leading to accidents.
●
Do not mix air in to the cooling cycle on installation or removal of the air conditioner.
If air is mixed in, the pressure in the cooling cycle will rise abnormally and may cause explosion and injuries.
●
Be sure to have the electrical wiring work done by qualified electrical installer, and use exclusive circuit.
Power source with insufficient capacity and improper work can cause electric shock and fire.
●
Use specified wire for electrical wiring, fasten the wiring to the terminal securely, and hold the cable securely in
order not to apply unexpected stress on the terminal.
Loose connections or hold could result in abnormal heat generation or fire.
●
Arrange the electrical wires in the control box properly to prevent them from rising. Fit the lid of the services
panel property.
Improper fitting may cause abnormal heat and fire.
●
Check for refrigerant gas leakage after installation is completed.
If the refrigerant gas leaks into the house and comes in contact with a fan heater, a stove, or an oven, toxic gas is produced.
●
Use the specified pipe, flare nut, and tools for R410A.
Using existing parts (R22) could cause the unit failure and serious accident due to explosion of the cooling cycle.
●
Tighten the flare nut according to the specified method by with torque wrench.
If the flare nut were tightened with excess torque, it could cause burst and refrigerant leakage after a long period.
●
Do not put the drainage pipe directly into drainage channels where poisonous gases such as sulfide gas can occur.
Poisonous gases will flow into the room through drainage pipe and seriously affect the user's health and safety. This can also
cause the corrosion of the indoor unit and a resultant unit failure or refrigerant leak.
●
Connect the pipes for refrigeration circuit securely in installation work before compressor is operated.
If the compressor is operated when the service valve is open without connecting the pipe, it could cause explosion and injuries due
to abnormal high pressure in the system.
●
Stop the compressor before removing the pipe after shutting the service valve on pump down work.
If the pipe is removed when the compressor is in operation with the service valve open, air would be mixed in the refrigeration circuit
and it could cause explosion and injuries due to abnormal high pressure in the cooling cycle.
●
Only use prescribed optional parts. The installation must be carried out by the qualified installer.
If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire.
●
Do not repair by yourself. And consult with the dealer about repair.
Improper repair may cause water leakage, electric shock or fire.
●
Consult the dealer or a specialist about removal of the air conditioner.
Improper installation may cause water leakage, electric shock or fire.
●
Turn off the power source during servicing or inspection work.
If the power is supplied during servicing or inspection work, it could cause electric shock and injury by the operating fan.
●
Do not run the unit when the panel or protection guard are taken off.
Touching the rotating equipment, hot surface, or high voltage section could cause an injury to be caught in the machine, to get
burned, or electric shock.
●
Shut off the power before electrical wiring work.
It could cause electric shock, unit failure and improper running.
●
Perform earth wiring surely.
Do not connect the earth wiring to the gas pipe, water pipe, lightning rod and telephone earth wiring. Improper earth could
cause unit failure, electric shock and fire due to a short circuit.
●
Earth leakage breaker must be installed.
If the earth leakage breaker is not installed, it can cause fire and electric shocks.
●
Use the circuit breaker of correct capacity. Circuit breaker should be the one that disconnect all
poles under over current.
Using the incorrect one could cause the system failure and fire.
●
Do not use any materials other than a fuse of correct capacity where a fuse should be used.
Connecting the circuit by wire or copper wire could cause unit failure and fire.
●
Do not install the indoor unit near the location where there is possibility of flammable gas leakages.
If the gas leaks and gathers around the unit, it could cause fire.
●
Do not install and use the unit where corrosive gas (such as sulfurous acid gas etc.) or flammable gas (such
as thinner, petroleum etc.) may be generated or accumulated, or volatile flammable substances are handled.
It could cause the corrosion of heat exchanger, breakage of plastic parts etc. And inflammable gas could cause fire.
●
Secure a space for installation, inspection and maintenance specified in the manual.
Insufficient space can result in accident such as personal injury due to falling from the installation place.
●
Do not use the indoor unit at the place where water splashes such as laundry.
Indoor unit is not waterproof. It could cause electric shock and fire.
●
Do not use the indoor unit for a special purpose such as food storage, cooling for precision
instrument, preservation of animals, plants, and a work of art.
It could cause the damage of the items.
●
Do not install nor use the system near equipments which generate electromagnetic wave or high harmonics.
Equipments like inverter equipment, private power generator, high-frequency medical equipment, or telecommunication
equipment might influence the air conditioner and cause a malfunction and breakdown. Or the air conditioner might
influence medical equipments or telecommunication equipments, and obstruct their medical activity or cause jamming.
●
Do not install the remote control at the direct sunlight.
It could cause breakdown or deformation of the remote control.
●
Do not install the indoor unit at the place listed below.
· Places where flammable gas could leak.
· Places where carbon fiber, metal powder or any powder is floated.
·
Place where the substances which affect the air conditioner are generated
such as sulfide gas, chloride gas, acid, alkali or ammonic atmospheres.
· Places exposed to oil mist or steam directly.
· On vehicles and ships
· Places where machinery which generates high harmonics is used.
●
Do not install the indoor unit in the locations listed below (Be sure to install the indoor unit
according to the installation manual for each model because each indoor unit has each limitation)
· Locations with any obstacles which can prevent inlet and outlet air of the unit
· Locations where vibration can be amplified due to insufficient strength of structure.
· Locations where the infrared receiver is exposed to the direct sunlight or the strong light beam. (in case of the
infrared specification unit)
· Locations where an equipment affected by high harmonics is placed. (TV set or radio receiver is placed within 5m)
· Locations where drainage cannot run off safely.
It can affect performance or function and etc.
.
●
Do not put any valuables which will break down by getting wet under the air conditioner.
Condensation could drop when the relative humidity is higher than 80% or drain pipe is clogged, and it damages user’s belongings.
●
Do not use the base frame for the outdoor unit which is corroded or damaged after a long period of use.
It could cause the unit falling down and injury.
●
Pay attention not to damage the drain pan by weld sputter when brazing work is done near the unit.
If sputter entered into the unit during brazing work, it could cause damage (pinhole) of drain pan and leakage of water.
To avoid damaging, keep the indoor unit packed or cover the indoor unit.
●
Install the drain pipe to drain the water surely according to the installation manual.
Improper connection of the drain pipe may cause dropping water into room and damaging user’s belongings.
●
Do not share the drain pipe for indoor unit and GHP (Gas Heat Pump system) outdoor unit.
Toxic exhaust gas would flow into room and it might cause serious damage (some poisoning or deficiency of oxygen) to
user’s health and safety.
●
Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.
If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can
occur, which can cause serious accidents.
●
For drain pipe installation, be sure to make descending slope of greater than 1/100, not to make traps,
and not to make air-bleeding.
Check if the drainage is correctly done during commissioning and ensure the space for inspection and maintenance.
●
Ensure the insulation on the pipes for refrigeration circuit so as not to condense water.
Incomplete insulation could cause condensation and it would wet ceiling, floor, and any other valuables.
●
Do not install the outdoor unit where is likely to be a nest for insects and small animals.
Insects and small animals could come into the electronic components and cause breakdown and fire. Instruct the user to
keep the surroundings clean.
●
Pay extra attention, carrying the unit by hand.
Carry the unit with 2 people if it is heavier than 20kg. Do not use the plastic straps but the grabbing place, moving the unit
by hand. Use protective gloves in order to avoid injury by the aluminum fin.
●
Make sure to dispose of the packaging material.
Leaving the materials may cause injury as metals like nail and woods are used in the package.
●
Do not operate the system without the air filter.
It may cause the breakdown of the system due to clogging of the heat exchanger.
●
Do not touch any button with wet hands.
It could cause electric shock.
●
Do not touch the refrigerant piping with bare hands when in operation.
The pipe during operation would become very hot or cold according to the operating condition, and it could cause a burn or frostbite.
●
Do not clean up the air conditioner with water.
It could cause electric shock.
●
Do not turn off the power source immediately after stopping the operation.
Be sure to wait for more than 5 minutes. Otherwise it could cause water leakage or breakdown.
●
Do not control the operation with the circuit breaker.
It could cause fire or water leakage. In addition, the fan may start operation unexpectedly and it may cause injury.
Always do it according to the instruction.
· Places where cosmetics or special sprays are
frequently used.
· Highly salted area such as beach.
· Heavy snow area
· Places where the system is affected by
smoke from a chimney.
· Altitude over 1000m
Drilling of holes and fixture of sleeve (Option parts)
Sleeve
Sleeve
Indoor side
Outdoor side
Thicknese of the wall
5
65
Installed state
When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe
hole sleeve sold separately.
Drill a hole with whole core drill. In case of right rear piping draw out,
cut off the lower and the right side
portions of the sleeve collar.
INSTALLATION MANUAL FOR WALL-MOUNTED UNIT (FDK)
This manual is for the installation of an indoor unit.
For electrical wiring work (Indoor), refer to the electrical wiring work installation manual. For remote
control installation, refer to the installation manual attached to a remote control. For wireless kit
installation, refer to the installation manual attached to a wireless kit. For electrical wiring work
(Outdoor) and refrigerant pipe work installation for outdoor unit, refer to the installation manual
attached to an outdoor unit.
① Before installation ③ Preparation before installation
④ Installation of indoor unit
② Selection of installation location for the indoor unit
ATTENTION
Select the suitable areas to install the unit under approval of the user.
Areas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user
to use a circulator if the ceiling height is over 3m to avoid warm air being accumulated on
the ceiling.
Areas where there is enough space to install and service.
Areas where it can be drained properly. Areas where drain pipe descending slope can be
taken.
Areas where there is no obstruction of airflow on both air return grille and air supply port.
Areas where fire alarm will not be accidentally activated by the air-conditioner.
Areas where the supply air does not short-circuit.
Areas where it is not influenced by draft air.
Areas not exposed to direct sunlight.
Areas where dew point is lower than around 23°C and relative humidity is lower than 80%.
This indoor unit is tested under the condition of JIS (Japan Industrial Standard) high humid-
ity condition and confirmed there is no problem. However, there is some risk of condensa-
tion drop if the air-conditioner is operated under the severer condition than mentioned
above.
Areas where TV and radio stays away more than 1m. (It could cause jamming and noise.)
Areas where any items which will be damaged by getting wet are not placed such as food,
table wares, server, or medical equipment under the unit.
Areas where there is no influence by the heat which cookware generates.
Areas where not exposed to oil mist, powder and/or steam directly such as above fryer.
Areas where lighting device such as fluorescent light or incandescent light doesn’t affect the
operation.
Check if the place where the air-conditioner is installed can hold the weight of the unit. If it is
not able to hold, reinforce the structure with boards and beams strong enough to hold it. If the
strength is not enough, it could cause injury due to unit falling.
Space for installation and service
50mm
or more
150mm
or more
100mm
or more
1800mm
or more
Secure a working space for inspection and maintenance.
(A beam from lighting device sometimes affects the infrared receiver for the wireless remote
control and the air-conditioner might not work properly.)
Accessory item
If there are 2 units of wireless type, keep them away for more than 6m to avoid malfunction due to
cross communication.
Front view for installing position and installing space UNIT: mm
Symbol
A
B
C
Gas piping
Liquid piping
Wall pulling hole for right rear piping
Symbol
D
E
Wall pulling hole for left rear piping
Drain piping
Installing installation board
D E AB C
530
450
185
190
43
170
585
13
Indoor unit
(Service space)
Installation board
142.5 142.5
150
50
9
47
268
47
100
210
55 55
170
210
435 435
(Service space)
80
(
Service space)
(Service space)
Type 15~56
Type 71, 90
Type 15~56
Type 15~56
Type 71, 90
Type 71, 90
(Service space)
Indoor unit
768
157
48240
6.7 322.4
214.5 214.5
883 157
10
47
53 77
47
150
50
(Service space)
(Service space)
15
(Service space)
100
783
715
759
Installation board
60
240
43
470 363.5363.5
568.5 568.5
D E CAB
537
528
Type 15~28 469
Type 36~56 475
●
Move the box as close to the installation area as possible packed.
●
If it must be unpacked, wrap the unit with a nylon sling, and be
careful not to damage the unit.
※ Do not hold fragile plastic parts, such as the side panel, blow
louver, etc.
●
If you need to lay the unit on a floor after unpacking, always put it
with the intake grille facing upward.
Adjustment of the installation board in the horizontal direction is to be conducted with five to
nine screws in a temporary tightened state.
●This unit cannot be installed directly onto a wall surface. Regardless of the surface it is to be
installed onto, you should use
installation board with the unit.
ATTENTION
Adjust so the board will be level by turning the board with the standard hole as the center.
530
450
768
470
60
Mating mark for level surfaceMating mark for level surface
Standard hole Standard hole
CAUTION
Completely seal the hole on
the wall with putty. Otherwise,
furniture, or other, may be
wetted by leaked water or
dewing.
putty
putty
Indoor side Outdoor side
10 1
For the mounting plate,
4mm (dia.) x 25mm (length)
For heat insulation, 50mm x 100mm
Tapping screw Insulation
1
Attached to the rear of the indoor unit.
Installation board
source