69
–
'17 • KX-T-264
-
130
-
'16 • PAC-T-251
(b) In case of CnT
③
operation permission/prohibition level + CnTA
③
operation permission/prohibition level
(
※
) Operation prohibition zone is determined by the OR judgment between CnT operation prohibition zone and CnTA
operation prohibition zone.
CnT
Operation permission
prohibition setting
CnTA
Operation permission/
prohibition setting
Operation permission/
prohibition zone
Operation permission Operation permission
Operation permission
Operation permission
Operation
permission
Operation
permission
Operation
permission
Operation
permission
Operation( )
permission
(20) Selection of cooling/heating external input function
(a) When “External input 1 setting: Cooling/heating” is set by the indoor unit function from remote control, the cooling or
heating is selected with CnT-6 or CnTA.
(b) When the external input 1 method selection: Level input is set by the indoor unit function:
・
CnT-6 or CnTA: OPEN → Cooling operation mode
・
CnT-6 or CnTA: CLOSE → Heating operation mode
(c) When the external input 1 method selection: Pulse input is set by the indoor unit function:
If the external input is changed OPEN → CLOSE, operation modes are inverted (Cooling → Heating or Heating →
Cooling).
Operation Operation Operation
Stop Stop Stop Stop
Operation
prohibition
Operation
prohibition
Operation
prohibition
Operation
prohibition
Operation
prohibition
Operation
prohibition
Operation
permission
Operation permission
Operation permission
Operation
permission
CnTA
Operation/
stop pulse
CnT
Operation permission/
prohibition level
Operation permission/
prohibition zone
Actual operation
Remote control
CnT
Operation/
stop pulse
CnTA
Operation permission/
prohibition level
Operation permission/
prohibition zone
Actual operation
Remote control
Remote
control ON
Remote
control OFF
Remote
control ON
Remote
ON ON
ON ON
ON ON ON
OFF OFF OFF OFF
OFFOFF
OFF
ON ON
OFF
ON ON ON ON ON
OFF OFF OFF OFF
OFF OFF
OperationOperation Operation Operation
Stop Stop Stop Stop Stop
(c) In case of CnT ③ operation permission/prohibition level > CnTA ② operation/stop pulse
(d) In case of CnT ② operation/stop pulse + CnTA ③ operation permission/prohibition level
Note (1) If it is prohibited by CnT, all “Operation” and “Stop” commands are not accepted.
(d) If the cooling/heating selection signal is given by the external input, the operation mode is transmitted to the remote
control.
■
Selection of cooling/heating external input function
Notes (1) Regarding the priority order for combinations of CnT and CnTA, refer to Page 64.
External input selection
External input selection
Cooling/heating selection
External input method
⑤ Level
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
⑥ Pulse
Operation
OFF
Cooling zone
Heating zone Cooling zone
Cooling zoneHeating zone Heating zone
OFF
ON
OFFOFF
ON ON
ON
Cooling
Heating Heating
Cooling
Cooling
Cooling
Auto
Auto
Cooling
Auto, cooling, dry mode command↑
from remote control
↑Heating, auto, heating mode command
from remote control
↑Set “Cooling/
Heating” “Pulse”
↑Auto, cooling, dry mode command
by remote control
↑Auto, heating mode
command by remote control
↑After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode.
During heating:: Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Heating
Cooling
Heating
Cooling
Cooling
(21) Room temperature detection temperature compensation during heating
With the standard
the compressor is turned ON/OFF with the thermostat setting temperature. When the thermostat
is likely to turn OFF earlier because the unit is installed at the ceiling where warm air tends to accumulate, the setting can be
changed with the wired remote control indoor unit function “
”. The compressor and the heater are turned ON/OFF at
one of the setting temperature +3, +2 or +1°C in order to improve the feeling of heating. The setting temperature, however, has
the upper limit of 30°C.
Compressor Compressor
Standard
Stop
Setting temperature
-1 +1
Room temperature (deg)
Stop
Setting temperature
+2 +4
When it is set at +3°C
(22) Return air temperature compensation
This is the function to compensate the deviation between the detection temperature by the return air temperature thermistor and
the measured temperature after installing the unit.
(a) It is adjustable in the unit of 0.5°C with the wired remote control indoor unit function “RETURN AIR TEMP”.
• +1.0°C, +1.5°C, +2.0°C • -1.0°C, -1.5°C, -2.0°C
(b) Compensated temperature is transmitted to the remote control and the compressor to control them.
Note (1) The detection temperature compensation is effective on the indoor unit thermistor only.
(19) Temporary stop input
In case of temporary stop, operation lamp of remote control lights, but indoor/outdoor unit stop the operation.
(a) In case of “level input” setting (Factory default)
Input signal to CnT-6 or CnTA is OFF → ON : Temporary stop
Input signal to CnT-6 or CnTA is OFF → ON : Normal operation
(b) In case of “pulse input” setting (Local setting)
It is effective only when the input signal is changed OFF→ON, and “temporary stop/normal operation” is inverted.
CnT-6 or CnTA input
OFF
ON
OFF
ONON
Actual operation
ON
ON
Te mporary stop
Te mporary stop
OFF
Remote control
ON
OFF
Normal operation/
Temporary stop zone
Normal
Te mporary stop
Normal
Te mporary stop
OFF
(23) Selection of cooling/heating external input function
(a) When “External input 1 setting: Cooling/heating” is set by the indoor unit function from remote control, the cooling or
heating is selected with CnT-6 or CnTA.
(b) When the external input 1 method selection: Level input is set by the indoor unit function:
・
CnT-6 or CnTA: OPEN → Cooling operation mode
・
CnT-6 or CnTA: CLOSE → Heating operation mode
(c) When the external input 1 method selection: Pulse input is set by the indoor unit function:
If the external input is changed OPEN → CLOSE, operation modes are inverted (Cooling → Heating or Heating →
Cooling).
(d) If the cooling/heating selection signal is given by the external input, the operation mode is transmitted to the remote
control.
■
Selection of cooling/heating external input function
External input selection
External input selection
Cooling/heating selection
External input method
⑤ Level
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External terminal input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
⑥ Pulse
Operation
OFF
Cooling zone
Heating zone Cooling zone
Cooling zoneHeating zone Heating zone
OFF
ON
OFFOFF
ON ON
ON
Cooling
Heating Heating
Cooling
Cooling
Cooling
Auto
Auto
Cooling
Auto, cooling, dry mode command↑
from remote control
↑Heating, auto, heating mode command
from remote control
↑Set “Cooling/
Heating” “Pulse”
↑Auto, cooling, dry mode command
by remote control
↑Auto, heating mode
command by remote control
↑After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode.
During heating:: Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Heating
Cooling
Heating
Cooling
Cooling
Notes (1) Regarding the priority order for combinations of CnT and CnTA, refer to Page 127.
CnT-6 or CnTA input
OFF
ON
OFF
ON
Actual operation
ON
ON
Temporary stop
Temporary stop
OFF
Remote control
ON
OFF