'17 • KX-T-264
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
None
Excessive noise/vibration (3/3)
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
[Adjustment
during commissioning]
Does noise/vibration occur when the
cooling/heating operation is performed
under anomalous
condition?
From previous page
YES
If insufcient cooling/
heating problem happens
due to anomalous operating
conditions at cooling
/heating, followings are
suspicious.
Excessive charged
amount of refrigerant
Insufficient charge
amount of refrigerant
Intrusion of air, nitrogen,
etc.
In such case, it is necessary
to recover refrigerant,
vacuum-dry and recharge
refrigerant.
* Since there could be
many causes of noise/
vibration, the above may
not cover all.
In such case, check the
conditions when, where,
how the noise/vibration
occurs according to
following check points and
ask our consultation.
Indoor/outdoor unit
Cooling/heating/fan
mode
Startup/stop/during
operation
Operating condition
(Indoor/outdoor
temperatures and
pressures)
Time it occurred
Operation data retained
by remote control or
Mente PC such as
compressor rotation
speed, heat exchanger
temperature, EEV
opening degree and etc.
Tone (If available, record
the noise)
Any other anomalies.
2. Error detection method
3
.
Condition of error displayed
4. Presumable cause
Note:
79