(11) Drain pump control
(a) This controlis operatedwhen the inverter frequency is other than0 rpsduring the cooling operation and automatic
coolinganddehumidifyingoperations.
(b) Drain pump ON condition continues for 5 minutes even when it entersthe OFF range accordingto (a) above after
turningthedrainpumpON,andthenstops.The5-minutedelaycontinuesalsointheeventofanomalousstop.
(c)
Thedrainpumpisoperatedwiththe5-minutedelayoperationwhenthecompressorischangedfromONtoOFF.
(d)Eveninconditionsotherthantheabove(suchasheating,fan,stop,coolingthermostatOFF),thedrainpumpcontrolis
performed by the drain detection.
(e)Followingsettingscanbemadeusingtheindoorfunctionsettingofthewiredremotecontrol.
(i)
(ii)
(iii)
(iv)
Note (1) Values in
〔
〕
arefortheRC-EX3Amodel.
ࠝStandardin coolingࠞ: Drain pump is run during cooling.
ࠝOperate in standard & heatingࠞ: Drain pump is run during cooling and heating.
ࠝOperate in heating & fanࠞ: Drain pump is run during cooling, heating and fan.
ࠝOperate in standard & fanࠞ: Drain pump is run during cooling and fan.
(12) Drain pump motor (DM) control
(a)
DraindetectionswitchisturnedONorOFFwiththeoatswitch(FS)andthetimer.
[
*
1]Draindetectionswitchisturned“ON”whentheoatswitch“Open”isdetectedfor3secondscontinuouslyin
the drain detectable space.
[
*
2]Draindetectionswitchisturned“OFF”whentheoatswitch“Close”isdetectedfor10secondscontinuously.
(i)Itdetectsalwaysfrom30secondsafterturningthepowerON.
1)Thereisnodetectionofanomalousdrainingfor10secondsafterturningthedrainpumpOFF.
2)Turningthedraindetectionswitch“ON”causestoturnONthedrainpumpforcibly.
3)Turningthedraindetectionswitch“OFF”releasestheforceddrainpumpONcondition.
Normal state
[*1] [*2]
Normal state
Drain detection switch ON
Stop
(1)
Indoor unit operation mode
Control A
Control B
Compressor ON
Compressor OFF
Cooling Dry HeatingFan
(2)
Notes (1) Including the stop from the cooling, dehumidifying, fan
and heating, and the anomalous stop
(2) Including the “Fan” operation according to the
mismatch of operation modes
(i)ControlA
1)Iftheoatswitchdetectsanyanomalousdrainingcondition,theunitstopswiththeanomalousstop(displaysE9)
andthedrainpumpstarts.Afterdetectingtheanomalouscondition,thedrainpumpmotorcontinuestobeON.
2)Itkeepsoperatingwhiletheoatswitchisdetectingtheanomalouscondition.
(ii) Control B
Iftheoatswitchdetectsanyanomalousdraincondition,thedrainpumpmotoristurnedONfor5minutes,andat10
secondsafterthedrainpumpmotorOFFitcheckstheoatswitch.Ifitisnormal,theunitisstoppedunderthenormal
modeor, if thereis anyanomalouscondition, E9 is displayed andthedrain pump motor isturnedON. (The ON
conditionismaintainedduringthedraindetection.)
(b)
IndoorunitperformsthecontrolAorBdependingoneachoperatingcondition.
(13) Operation check/drain pump test run operation mode
(a)
If the power is turned on by the DIP switch(SW7-1) on the indoor unit control PCB when electric power source is
supplied,it entersthemodeof operationcheck/drainpumptest run. Itisineective(prohibited) tochangetheswitch
afterturningpoweron.
(b)Whenthecommunicationwiththeremotecontrolhasbeenestablishedwithin60secondsafterturningpoweronbythe
DIPswitch(SW7-1)ON,itenterstheoperationcheckmode.Unlesstheremotecontrolcommunicationisestablished,
it enters the drain pump test run mode.
Note (1) To select the drain pump test run mode, disconnect the remote control connector (CnB) on the indoor unit PCB to shut down the remote control
communication.