'22 • PAC-SM-412
-
25
-
(37) Motion sensor control (RC-EXZ3A and RCN-E2 only)
Thesensordeterminesthepresenceofpeopleandtheamountofactivity,andthefollowingcontrolsaredonebythemotionsensor.
Followingsettingsarenecessarytoactivatemotionsensorcontrol.
(a)Infrared(motion)sensorsetting:Installationsettingofremotecontrol
Theindoorunitwhichissetto“Enable”becomevalid.
(b)Infrared(motion)sensorcontrol:Energy-savingsettingofremotecontrol
Thefunctionwhichissetto“Enable”becomevalid.
①
②
③
Set
button.
The Infrared sensor control screen and contents of the
current settings are displayed.
Enable/disable power control.
Enable/disable auto-off.
After you set each item, tap the
The display returns to the Energy-saving setting
menu screen.
Infrared sensor control
Set Back
EnableDisable
EnableDisable
Select the item.
Power control
Auto-off
1
2
RCN-E2
RC-EXZ3A
1. Set indoor functions
①
Press the ON/OFF button to stop the unit.
②
Press the desired one of the buttons shown item 2. while holding down the
FUNCTION SETTING switch.
③
Use the selection buttons, ▲ and ▼, to change the setting.
④
Press the SET button.
The buzzer on the remote control signal receiver beeps twice, and the LED
①
④
②
③
②
②
2. Setting details
Button
Number
indicator
Function setting
SILENT
00 Infrared sensor setting (Motion sensor setting) : Disable
01 Infrared sensor setting (Motion sensor setting) : Enable
HI POWER
00 Infrared sensor control (Motion sensor control) : Disable
01 Infrared sensor control (Motion sensor control) : Power control only
02 Infrared sensor control (Motion sensor control) : Auto OFF only
03 Infrared sensor control (Motion sensor control) : Power control and Auto OFF
TOP screen
Menu
Service setting
Installation settings
Service password
②
Installation settings menu #2
Installation settings
Address setting of main IU
IU back-up function
Infrared sensor setting
Previous Back
Select the item.
⑰
Infrared (motion) sensor setting
Select the item.
Infrared sensor setting
Disable
Enable
Back
Menu
Direction
Cooling
16:14
(Mon)
F1: High power F2: Energy-saving
Timer
Set temp
TOP screen
Menu
Energy-saving setting
or
Motion sensor controlInfrared sensor control
3
Now stopping.