'22 • PAC-SM-412
-
26
-
(i) Powersaving
/
comfort control
Thesettemperatureisadjustedaccordingtothepresenceofpeopleandtheiramountofactivitydetectedbytheinfrared(motion)
sensor.
(ii)Auto-ocontrol
Whennoactivityisdetectedfor1hour,unitwillgostand-bymode.
Unit will re-start operation automatically with the
originalsettemperaturebyactivitydetection during the stand-by mode.Whenstand-bymodecontinuesfor12hours,
unit stops.
Compressorkeepsstoppedregardlessofthesettemperature.
Notes(1)Whenthefollowingoperationsareset,powersavingcontrolwillbecanceled.
Energy-saving,Homeleavemode,Warm-upcontrol,Coolingoperationcheck.
WhentheoperationmodeischangedDRYorFAN.
(2)Notoperablewhiletheair-conditionerisOFF.
Low
When the extent of human
activity is low
High
When the extent of human
activity is high
None
When there is no one in the
room
When the “None” continues for 1 hour, the
FANSPEEDissetLo.
MODE:AUTO/COOL/HEAT mode operation
COOL
HEAT
Set
temperature
-3ºC
33ºC
15ºC
+3ºC
Heat Source & Activity Low
Normal
High None