• Lossnay can be
started/stopped by an A-con-
trol remote controller or a K-
control remote controller.
•
Lossnay High or Low fan
speed can be selected from
the A-control remote controller.
• Lossnay stand-alone opera-
tion is permitted from the A-
control remote controller.
* Neither PZ-60DR-E nor PZ-
41SLB-E can be used.
Level sig-
nal output
device
(other
manufac-
turer's
PAC, etc.)
or pulse
signal out-
put device
(building
control
system,
etc.)
Systems
interlock
ed with
external
device
(air con-
dition-
ing
units)
—
—
22
—
—
6. Fundamentals of operation
Description of the circuit operation
(1) System Configuration
Lossnay operates through the following system.
System
Classification
Details
1 Lossnay
unit
1 Remote
controller
Two
remote
con-
trollers
system
1 Lossnay
unit
2 Remote
controllers
Multiple
units
system
Multiple
Lossnay
units
System Diagram
Remote controller
: PZ-60DR-E or PZ-41SLB-E
Transmission cable terminal
blocks between Lossnay unit
M-NET : M-NET transmission cable
terminal block
R : Remote controller
(
PZ-60DR-E or PZ-41SLB-E)
• One remote controller oper-
ates one Lossnay unit.
• Two remote controllers oper-
ate one Lossnay unit. (Last
touch priority operation)
*
PZ-60DR-E and PZ-41SLB-E
cannot be used together.
Lossnay
remote
controller
(PZ-60DR-
E, or PZ-
41SLB-E)
Lossnay
remote
controller
(PZ-60DR-
E or PZ-
41SLB-E)
• A maximum of 15 Lossnay
units can be operated by a
single remote controller.
(Group operation)
• All units will operate in the
same mode.
Lossnay
remote
controller
(PZ-60DR-
E or PZ-
41SLB-E)
Features
Prepared
Parts
• Lossnay is started/stopped
by a signal (*1) from an
external device.
• Having a remote control per-
mits last touch priority opera-
tion with the external device
and the remote controller.
• A maximum of 15 Lossnay
units can be operated.
*1: An uncharged a-contact,
12 V DC or 24 V DC level
signal, or an uncharged a-
contact, 12 V DC or 24 V
DC pulse signal.