1-1 Outdoor coil temperature
To obtain data on the outdoor coil temperature,
add the number of bits of lighting LEDs, and
see the graph to find the temperature.
1-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan
rotational frequency.
1-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of light-
ing LEDs. During the compressor operation time indication, SW2 is not available.
1-4 Check code indication
● When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes
time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and
SW3-2 are OFF, the check code is indicated.
● If the outdoor controller board receives the compressor ON command from the indoor controller board during check
mode the indication changes to output state indication.
● By pressing SW2 during normal operation. operation will continue.
● The latest check code is indicated.
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
50
Fan output step (bit)
Fan rotational frequency (rpm)
100 150 200 250
800
600
400
200
0
212
˚F
Temperature
176
140
104
68
32
0
Number of bits
50 100 150 200 255
-4
-40
(Short 38 bits)
(Open 219 bits)
1 PUH18EK PUH24EK
PUH24EK
1
2 PUH30EK PUH36EK PUH42EK PUH42EK7
PUH30EK1 PUH36EK1 PUH42EK1 PUH42EK71
PUH30EK2 PUH36EK2
OC245-C--1.qxp 02.12.19 9:58 AM Page 21