EasyManua.ls Logo

Mitsubishi NF-S Series - Page 20

Mitsubishi NF-S Series
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
Type
Frame (A)
NF100-HP T/ANF100-HP
Low-inst
Standard
Mag-Only
Generator
690V
500V
440V
400V
230V
AC Breaking
capacity (kA rms)
IEC60947-2
Icu/Ics
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Thermal, magnetic
Fixed ampere rating and
instantaneous
15 225 ± 45
20 300 ± 60
30 450 ± 90
40 600 ± 120
50 750 ± 150
60 900 ± 180
75 1125 ± 225
100 1500 ± 300
Magnetic
Fixed ampere rating and
instantaneous
234
Rated insulation voltage Ui (V) AC
5/3
30/15
50/25
50/25
100/50
234
690
15, 20, 30, 40, 50, 60, 75, 100
Rated current In (A)
15 ~ 20, 20 ~ 25, 25 ~ 40
40 ~ 63, 63 ~ 80, 80 ~ 100
690
5/3
30/15
50/25
50/25
100/50
234
Thermal, magnetic
Adjustable ampere rating
and fixed instantaneous
NF100-RP
15, 20, 30, 40, 50, 60, 75, 100
690
42/42
125/125
125/125
125/125
23
Thermal, magnetic
Fixed ampere rating and
instantaneous
15 ~ 20 225 ± 45
20 ~ 25 300 ± 60
25 ~ 40 375 ± 75
40 ~ 63 600 ± 120
63 ~ 80 945 ± 189
80 ~ 100 1200 ± 240
15 225 ± 45
20 300 ± 60
30 450 ± 90
40 600 ± 120
50 750 ± 150
60 900 ± 180
75 1125 ± 225
100 1500 ± 300
100
15 150 ± 30
20 200 ± 40
30 300 ± 60
40 400 ± 80
50 500 ± 100
60 600 ± 120
75 750 ± 150
100 1000 ± 200