EasyManua.ls Logo

Mitsubishi NF-S Series - 7.7 MCCBs for Thyristor Circuits

Mitsubishi NF-S Series
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62
instantaneous supply voltage (V), according to the
phase angle at the instant of circuit closure. This
charge results in a large surge current. If the circuit is
closed at the peak (E
m
) of the supply voltage (V), the
surge current (i), according to transient phenomena
theory, is:
2 E
m
i =
t
2L
R
ε
C
4L
– R
2
2L
sin
t
C
4L
– R
2
From Fig. 7.12, the maximum value (i
m
) is:
E
m
i
m
=
R
ε
C
L
R
arctan
C
C
4L
– R
2
4L
– R
2
and appears at time t = t
0
where:
2L
t
0
=
R
arctan
C
C
4L
– R
2
4L
– R
2
Although V is not constant, τ
0
is extremely small, so
that V = E
m
can be assumed for the transient dura-
tion; similarly, the conduction time can be assumed
as 2τ
0
. Thus, an MCCB for use in a capacitive circuit
must have an instantaneous-trip current of greater
than i
m
x 2τ
0
.
Example: MCCB selection for a 3-phase 230V 50Hz
150 kVA capacitor circuit.
From Table 7.4, C = 0.9026 x 10
–2
(F) and I =
377(A).
The values of R and L in the circuit must be esti-
mated, and for this purpose it is assumed that the
short-circuit current is approximately 100 times the
circuit capacity – i.e., 50,000A.
Z = R
2
+ (2πfL)
2
50,000 =
3 Z
V
thus: Z = = 2.66 x 10
–3
3 x 50,000
230
since: E
m
=
obtained from their respective formulas as,
V = 188, i
m
and τ
0
can be
3
2
and assuming:
then: 2πfL = 2.60 x 10
–3
thus: R = 5.21 x 10
–4
L = 8.29 x 10
–6
(H)
= 5
R
2πfL
i
m
=6200A
τ
0
= 4.27 x 10
–4
(s).
Since current-flow duration is approximately 2τ
0
,
an MCCB is selected with a latching time of 0.001
seconds at 6200A. The Type NF630-SP is suitable,
having a latching time of 0.0029 seconds at 10,000A.
Even with a shorter latching time, tripping is unlikely
under the application of the above current, but selec-
tion of an MCCB with an instantaneous-trip current of
greater than
M2
6200
= 4400A is recommended for an
adequate safety margin. Such an MCCB will be rated
at 600A. Accordingly, in this example the Type NF630-
SP, rated at 600A, is selected. Table 7.4 is a basis for
selection, but since, in cases where the short-circuit
capacity of the circuit is considerably higher than that
of the MCCB, spurious tripping due to the switching
surge may occur, it is also necessary to make calcu-
lations along the lines of the above example.
E
m
V
c
iL R
C
Fig. 7.11 PF Correction Capacitor
V
c
i
i
m
τ
o
FIg. 7.12 Currents and Voltages
7.7 MCCBs for Thyristor Circuits
Both overcurrent and overvoltage protection must be
provided for these elements. MCCBs can be used
effectively for overcurrent, although application de-
mands vary widely, and selection must be made care-
fully in each case. Overvoltage protection must be
provided separately; devices currently in use include
lightning arresters, dischargers, RC filters and oth-
ers.
1. MCCB Rated Currents
A primary factor determining the rated current of the
MCCB to be used is the question of AC-side or DC-
side installation. AC-side installation permits a lower
rating, which is a considerable advantage. Fig. 7.13
shows both AC and DC installation (MCCBs 1 and 2);
Table 7.5 gives a selection of circuit formats and cur-
rent configurations; using this table it is possible to
determine the MCCB rating for either MCCB 1 or 2,
as required. The current curve of the thyristor (aver-
age current is usually given) and the tripping curve of
the MCCB should be rechecked to ensure that there
is no possibility of overlap.
When an overcurrent is due to a fault in the load,
causing a danger of thermal destruction of the circuit
elements, either AC or DC protection is adequate,
provided the parameters are properly chosen. When

Related product manuals