EasyManua.ls Logo

Mitsubishi NF-S Series - 7 Selection; For Motor Branch Circuits; For Lighting and Heating Branch Circuits

Mitsubishi NF-S Series
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
7. SELECTION
In selecting MCCBs for a particular application, in
addition to purely electrical aspects of load and distri-
bution conductor systems, physical factors such as
panelboard configuration, installation environment,
ambient-temperature variations, vibration, etc. must
also be considered.
MCCBs are rated for an ambient of 40°C, and
where panelboard internal temperatures may exceed
this, the MCCBs installed should be derated in accor-
dance with Table 7.1.
1. Actual load currents may exceed the nominal-val-
ues.
2. Load currents may increase with time, due to dete-
rioration of load devices (i.e., friction in motors).
3. Source voltage and frequency may vary.
7.1 Motor Branch Circuits
The following discussion assumes single motors and
cold-start operation.
7.1.1 General Considerations
The starting current (I
MS
) and time (T
MS
) for the mo-
tor, and its full-load current, dictate the rated current,
long-delay trip and instantaneous-trip curves for the
MCCB as shown in Fig. 7.2. A safety-margin of up to
50% should be considered for the starting time, to
allow for voltage variations and increase in load fric-
tion.
The instantaneous-trip curve should be at least 1.4
x normal starting current to allow for the effect of the
DC component attendant to the low power factor
(about 0.3) of the starting current. For -delta start-
ing the unphased-switching allowance increases the
1.4 margin to 1.9. For running restarting the unphased-
switching allowance increases the factor to 2.4.
Rated currents
MCCB trip curve
Starting current
and long-delay trip
Inrush and
inst. trip
Motor
starting
current
T
MS
I
MS
Current
Time
Fig. 7.2 MCCB and Motor Starting
7.1.2 Motor Breaker
Where starting times are relatively short and currents
are small, the Mitsubishi M Line motor breakers can
be used without the need for a motor starter.
7.2 For Lighting and Heating Branch Cir-
cuits
In such circuits, switching-surge magnitudes and times
are normally not sufficient to cause spurious tripping
problems; however, in some cases, such as mercury-
arc lamps or other large starting-current equipment,
the methods presented in §7.1 above should be con-
sidered.
In general, branch MCCBs should be selected so
that the total of ratings of the connected loads is not
more than 80% of the MCCB rating.
Fig. 7.1 MCCB Selection Consideration
Table 7.1 MCCB Deratings Due to Installation
Factors
Panelboard max.
internal temp. (°C)
50
55
60
Load allowable, due to
panelboard temp. (%)
90
80
70
Supply
system
Ambient
temperature
Main,submain
or branch use
Ambient
conditions
Wire
connection
Load
current
Operation
conditions
Load
Short circuit
Installation and
connection style
Service
purpose
Regulations
?

Related product manuals