21
Type
Rated current In (A)
Rated insulation voltage Ui (V) AC
Low-inst
Standard
Mag-Only
Generator
690V
500V
440V
400V
230V
Frame (A)
AC Breaking
capacity (kA rms)
IEC60947-2
Icu/Ics
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
Number of poles
Automatic tripping
device
Rating (A) and
Inst. (A)
160
NF160-SP
125, 150, 160
690
15/8
25/13
30/15
50/25
234
Thermal, magnetic
Fixed ampere rating and
instantaneous
Magnetic
Fixed ampere rating and
instantaneous
125 1250 ± 250
160 1600 ± 320
NF160-SP T/A
100 ~ 125, 125 ~ 160
690
15/8
25/13
30/15
50/25
234
Thermal, magnetic
Adjustable ampere rating and
fixed instantaneous
NF160-HP
125, 150, 160
690
5/3
30/8
50/13
50/13
100/25
234
Thermal, magnetic
Fixed ampere rating and
instantaneous
125 1750 ± 350
150 2100 ± 420
160 2240 ± 448
100 ~125 1400 ± 280
125 ~ 160 1400 ± 280
125 1750 ± 350
150 2100 ± 420
160 2240 ± 448
234 234
Magnetic
Fixed ampere rating and
instantaneous
125 1250 ± 250
160 1600 ± 320