42
Selective interruption combinations (MCCB-MCCB)
230VAC (Sym. kA)
NF100-SEP
NF100-HEP
NF250-SEP
NF250-HEP
NF400-SEP
NF400-HEP
NF630-SEP
NF630-HEP
NF800-CEP
NF800-SEP
NF800-HEP
NF1000-SS
NF1200-SS
NF1600-SS
Main Breaker
Branch
Breaker
NF30-SP
NF50-HRP
NF160-SP
NF160-SP T/A
NF250-SP
NF250-SEP
NF250-SP T/A
NF250-HP
NF250-HEP
NF250-HP T/A
NF400-SP
NF630-HEP
NF400-SEP
NF400-HEP
NF250-CP
NF250-CP T/A
NF400-CP
NF630-CP
NF100-RP
NF100-UP
NF225-RP
NF225-UP
NF400-UEP
NF630-UEP
NF800-UEP
NF630-SP
NF630-SEP
NF50-CP
NF60-CP
NF100-CP
NE100-CP T/A
NF160-HP
NF160-HP T/A
NF100-SP
NF100-SP T/A
NF100-SEP
NF100-HP
NF100-HP T/A
NF100-HEP
NF50-HP
NF60-HP
Icu(kA) 50 100 50 100 85 100 85 100 50 85 100 125
5 1.61.63.53.55555555 5
25 1.6 1.6 3.5 3.5 10 10 20 20 20 20 20 25
85 – – 3.5 3.5 10 10 20 20 20 65 65 85
50 – – 3.5 3.5 7.5 7.5 15 15 15 15 15 50
100 – – 3.5 3.5 10 10 25 25 25 25 25 100
50 ––––6.46.4101010101050
50 ––––––101010101050
50 ––––6.46.4101010101050
50 ––––6.46.4101010101050
100 ––––6.46.4101010101050
100 ––––––101010101050
100 ––––6.46.4101010101050
100 ––––6.46.4101010101050
85 ––––––––10101020
85 ––––––9.59.510101020
100 ––––––9.59.510101020
85 ––––––––––– 20
100 ––––––––––– 20
5 1.61.63.53.55555555 5
25 – – 3.5 3.5 7.5 7.5 10 10 10 10 15 25
30 ––––––7.57.57.57.57.525
30 ––––6.46.47.57.57.57.57.525
50 ––––––––10101020
50 ––––––––––– 20
125 – – 3.5 3.5 22 22 65 65 50 85 85 125
200 – – 3.5 3.5 22 22 65 65 50 85 85 125
125 ––––––––185050125
200 ––––––––185050125
200 ––––––––15151525
200 ––––––––––– 20
200 ––––––––––– –
S
C
U
Icu : Rated breaking capacity
Note : Reted currents main breakers are maximum values.