44
Selective interruption combinations (ACB-MCCB)
230VAC (Sym. kA)
NF100-CP
NF100-SP
NF100-SP T/A
NF100-HP
NF100-HP T/A
NF100-SEP
NF100-HEP
NF160-SP
NF160-SP T/A
NF160-HP
NF160-HP T/A
NF250-CP
NF250-CP T/A
NF250-SP
NF250-SP T/A
NF250-HP
NF250-HP T/A
NF250-SEP
NF250-HEP
NF400-CP
NF400-SP
NF400-SEP
NF400-HEP
NF630-CP
NF630-SP
NF630-SEP
NF630-HEP
NF800-CEP
NF800-SEP
NF800-HEP
25
50
50
100
100
50
100
50
50
100
100
30
30
50
50
100
100
50
100
50
85
85
100
50
50
85
100
50
85
100
AE630-SS
65
15(25)
16(50)
16(50)
24(65)
24(65)
16(50)
24(65)
15(50)
15(50)
9.4(65)
9.4(65)
9.4(30)
9.4(30)
15(50)
15(50)
9.4(65)
9.4(65)
15(50)
9.4(65)
AE1000-SS
65
25
45(50)
45(50)
65
65
50
65
24(50)
24(50)
25(65)
25(65)
22.5(30)
22.5(30)
24(50)
24(50)
25(65)
25(65)
24(50)
25(65)
15(50)
15(65)
15(65)
15(65)
15(65)
15(65)
AE1250-SS
65
25
50
50
65
65
50
65
30(50)
30(50)
40(65)
40(65)
30
30
30(50)
30(50)
40(65)
40(65)
30(50)
40(65)
20(50)
20(65)
20(65)
20(65)
18.7(50)
18.7(50)
18.7(65)
18.7(65)
18.7(50)
18.7(65)
18.7(65)
AE1600-SS
65
25
50
50
65
65
50
65
42(50)
42(50)
65
65
30
30
42(50)
42(50)
65
65
42(50)
65
30(50)
30(65)
30(65)
30(65)
24(50)
24(50)
24(65)
24(65)
24(50)
24(65)
24(65)
AE2000-SS
85
25
50
50
85
85
50
85
50
50
85
85
30
30
50
50
85
85
50
85
48(50)
48(65)
48(65)
48(65)
30(50)
30(50)
30(65)
30(65)
30(50)
30(65)
30(65)
AE2500-SS
85
25
50
50
85
85
50
85
50
50
85
85
30
30
50
50
85
85
50
85
50
70
70
70
40(50)
40(50)
40(65)
40(65)
40(50)
40(65)
40(65)
AE3200-SS
85
25
50
50
85
85
50
85
50
50
85
85
30
30
50
50
85
85
50
85
50
85
85
85
50
50
60(65)
60(65)
50
60(65)
60(65)
AE4000-SSC
85
25
50
50
85
85
50
85
50
50
85
85
30
30
50
50
85
85
50
85
50
85
85
85
50
50
85
85
50
85
85
Branch Breaker
Main Breaker
Ics(kA)
Icu
(kA)
The values in the table represent the max. rated current for both Series AE-SS air circuit breakers and branch breakers, and the
selective co-ordination applies when the AE-SS series air circuit breakers instantaneous pick up is set to maximum.
The numerals shown in parentheses are for AE-SS with MCR. (When set MCR.)