Page #146 background imageLoading...
Page #146 background image
7 - 2 7 - 2
MELSEC-Q
7 TROUBLESHOOTING
7
[Display contents]
• Module
The following information is displayed.
Model name : Installed module model name
Header I/O No. : Relevant module's header Input / Output signal
No.
Installation position : The slot position where the module is installed.
Product information : Product information
The last character of the product information
indicates the function version of the module.
(Example) If the last character is "B," it
means that the module is of
function version B.
• Module access
If the QD51 (-R24) System Down signal (X0D) is OFF and the QD51 (-
R24) operating status signal (X0E) is ON, then Accessible is displayed.
• I/O address verification status
This displays whether the module the user has set the parameters for
matches the module that is installed or not.
• Latest error code
Displays the error code for the most recent error that has occurred.
• Error display
Displays the error codes for the error that have occurred with all the used
functions as the object.
(2) If you are checking by the hardware information screen in the GX
Developer diagnostic function
[Start Procedure]
GX Developer [Diagnostics] [System Monitor]
Module Detailed Information
Hardware Information

Table of Contents

Other manuals for Mitsubishi QD51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi QD51 and is the answer not in the manual?

Mitsubishi QD51 Specifications

General IconGeneral
BrandMitsubishi
ModelQD51
CategoryController
LanguageEnglish

Related product manuals