241
-
'16 • SCM-T-199
None
Power source system error
(Power source to remote control)
Keeps ashing
3-time ash
Outdoor
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Isn't there any
loose connection of remote
control wires?
Isn't remote
control wire broken or
short-circuited?
Disconnect remote
control wires.
NO
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
YES
YES
NO
Is DC180V
between
-
of CNW1
(FDTC:CNW2)?
YES
NO
NO
Correct.
Replace wires.
Replace remote control.
Defective indoor power
PCB
Replace.
Defective indoor control
PCB
Replace.
2. Error detection method
3 .
Condition of error displayed
4. Presumable cause
Remote control wire
breakage/short-circuit
Defective remote control
Malfunction by noise
Faulty indoor power PCB
Broken harness
Faulty indoor control PCB
Note:
Error code
Remote control:
LED Green Red
Indoor
Content

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM45ZS-S and is the answer not in the manual?

Mitsubishi SCM45ZS-S Specifications

General IconGeneral
BrandMitsubishi
ModelSCM45ZS-S
CategoryAir Conditioner
LanguageEnglish