46
-
'18 • SRK-T-250
'09•SRK-DB-087D
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
(3) Correction relative to frosting on outdoor heat exchanger during heating
How to obtain the cooling and heating capacity
Piping length [m]
Cooling
Heating
7
1.0
1.0
10
0.99
1.0
15
0.975
1.0
20
0.965
1.0
25
0.95
1.0
Air inlet temperature of
outdoor unit in °C WB
Adjustment coefficient
-15
0.95 0.95 0.94 0.93 0.91 0.88 0.86 0.87 0.92 1.00
-10 -9 -7 -5 -3 -1 13
5 or more
Example : The net cooling capacity of the model SRK35ZS-W
with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C
and outdoor dry-bulb temperature 35˚C is
Net cooling capacity =
SRK35ZS-W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SRK Series and is the answer not in the manual?

Mitsubishi SRK Series Specifications

General IconGeneral
TypeSplit System
Cooling TechnologyInverter
Power Supply220-240V, 50Hz
RefrigerantR32
Cooling CapacityVaries by model
Heating CapacityVaries by model
Energy Efficiency Ratio (EER)Varies by model
Coefficient of Performance (COP)Varies by model
Noise Level (Indoor Unit)Varies by model
Noise Level (Outdoor Unit)Varies by model
Indoor Unit Dimensions (W x H x D)Varies by model
Outdoor Unit Dimensions (W x H x D)Varies by model
Indoor Unit WeightVaries by model
Outdoor Unit WeightVaries by model

Related product manuals