 107 
-
(e) Self-diagnosis table
When this air conditioner performs an emergency stop, the reason why the emergency stop occurred is displayed by the flashing of
display lights. If the air conditioner is operated using the remote control 3 minutes or more after the emergency stop, the trouble
display stops and the air conditioner resumes operation. 
(1)
Notes (1)The air conditioner cannot be restarted using the remote control for 3 minutes after operation stops.
(2)The wired remote control is optional parts.
When a heat exchanger sensor wire disconnection is detected while 
operation is stopped. (If a temperature of –20ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) (Not displayed 
during operation.)
When a room temperature sensor wire disconnection is detected while 
operation is stopped. (If a temperature of –20ºC or lower is detected for 
15 seconds, it is judged that the wire is disconnected.) (Not displayed 
during operation.)
• Broken heat exchanger sensor 
wire, poor connector 
connection
• Broken room temperature 
sensor wire, poor connector 
connection
Heat exchanger 
sensor error
Room 
temperature 
sensor error
When conditions for turning the indoor unit’s fan motor on exist during 
air conditioner operation, an indoor unit fan motor speed of 300 rpm or 
lower is measured for 30 seconds or longer. (The air conditioner stops.)
• Defective fan motor, poor 
connector connection
Indoor fan 
motor error
ON
1 time
flash
ON
2 time
flash
ON
6 time
flash
When an outdoor temperature sensor wire disconnection is detected 
while operation is stopped. (If a temperature of –40ºC or lower is 
detected for 15 seconds, it is judged that the wire is disconnected.) (Not 
displayed during operation.)
• Broken outdoor air temp. 
sensor wire, poor connector 
connection
Outdoor air 
temperature 
sensor error
1 time
flash
Keeps
flashing
When a sensor wire disconnection is detected while operation is 
stopped. (If a temperature of –50ºC or lower is detected for 15 seconds, 
it is judged that the wire is disconnected.) (Not displayed during 
operation.)
• Broken heat exchanger sensor 
wire, poor connector 
connection
Outdoor heat 
exchanger 
sensor error
2 time
flash
Keeps
flashing
When a compressor discharge pipe sensor wire disconnection is 
detected for 15 seconds or longer (less than 7ºC) after the outdoor 
unit’s speed has continued at 0 rps or higher for 9 minutes. 
(The air conditioner stops.)
• Broken discharge pipe sensor 
wire, poor connector 
connection
Discharge pipe 
sensor error
4 time
flash
Keeps
flashing
The inverter output current (compressor motor current) exceeds the set 
value during compressor start. 
(The air conditioner stops.)
• Compressor locking, open 
phase on compressor output, 
shortcircuit on power 
transistor, closed service valve
Current Cut
1 time
flash
ON
When there is an emergency stop caused by trouble in the outdoor unit, 
or the input current value is found to be lower than the set value 
continuously for 3 minutes or longer.
 (The air conditioner stops.)
• Broken power transistor, 
broken compressor wire
• Broken discharge pipe sensor 
wire, poor connector 
connection
• Compressor blockage
Trouble of 
outdoor unit
2 time
flash
ON
When the value of the discharge pipe sensor exceeds the set value. 
(The air conditioner stops.)
• Gas shortage, defective 
discharge pipe sensor, closed 
service valve
Over heat of 
compressor
ON
5 time
flash
6 time
flash
ON
When there is no signal between the indoor unit’s board and outdoor 
unit’s board for 10 seconds or longer (when the power is turned on), or 
when there is no signal for 1 minute 50 seconds or longer (during 
operation)(the compressor is stopped).
• Defective power supply, 
Broken signal wire, defective 
in/outdoor unit boards
Error of signal 
transmission
If the compressor motor’s magnetic pole positions cannot be correctly 
detected when the compressor starts. 
(The air conditioner stops.)
• Defective compressor
• Open phase on compressor
• Defective outdoor unit boards
Rotor lock
2 time
flash
2 time
flash
When the outdoor unit’s fan motor sped continues for 30 seconds or 
longer at 75 rpm or lower. (3 times) (The air conditioner stops.)
• Defective fan motor, poor 
connector connection
Outdoor fan 
motor error
7 time
flash
ON
Indoor unit display panel
Description
of trouble
Cause Display (flashing) condition
RUN 
light
TIMER
light
When the inverter command speed is 20 rps or less and the current save 
has operated. (the compressor stops)
• Overload operation
• Overcharge
• Compressor locking
Current safe 
stop
3 time
flash
E 6
E 7
E 16
E 38
E 37
E 39
E 42
E 59
E 36
E 5
E 60
E 48
The wired remote control wire Y is open. The wired remote control 
wires X and Y are reversely connected. Noise is penetrating the wired 
remote control lines. The wired remote control or indoor control PCB is 
faulty. (The communications circuit is faulty.)
• Broken wired remote control 
wire, defective indoor unit 
boards
Error of wired 
remote control 
wiring
—
—
E 1
E 58ON
Wired 
remote 
control 
display