EasyManuals Logo

Mitsubishi SRK50A User Manual

Mitsubishi SRK50A
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
1-61
(7) Standard operation data
(a) Heat pump type (220/240V)
Item
Model
SRK208HENF-L SRK288HENF-L SRK328HENF-L SRK408HENF-L
Cooling ––––
High pressure (kgf/cm
2
G)
Heating 15 ~ 17 17 ~ 19 17 ~ 19 18 ~ 20
Cooling 4.5 ~ 5.5 4 ~ 5 4.5 ~ 5.5 4 ~ 5
Low pressure (kgf/cm
2
G)
Heating ––––
Cooling 14 ~ 16 11 ~ 15 12 ~ 16 12 ~ 16
Heating 16 ~ 18 18 ~ 22 18 ~ 22 18 ~ 22
Cooling 3.4/3.6 4.5/4.6 6.9/6.9 6.4/6.4
Running current (A)
Heating 3.0/3.4 4.0/4.1 6.1/6.1 6.5/6.5
(220V/240V)
Note (1) The data are measured at following conditions
Ambient air temperature
Indoor side: Cooling ... 27°C DB, 19°C WB, Heating ... 20°C DB
Outdoor side: Cooling ... 35°C DB, 24°C WB, Heating ... 7°C DB, 6°C WB
Temp. difference between suction
air and discharge air (˚C)
(b) Cooling only type (220/240V)
Item
Model
SRK208CENF-L SRK258CENF-L SRK288CENF-L SRK328CENF-L SRK408HENF-L
High pressure (kgf/cm
2
G) –––––
Low pressure (kgf/cm
2
G) 5 ~ 6 5 ~ 6 4 ~ 5 5 ~ 6 4 ~ 5
11 ~13 12 ~ 16 13 ~ 17 12 ~ 16 13 ~ 17
Running current (A) 2.5/2.6 3.3/3.4 4.1/4.2 4.3/4.4 6.4/6.4
(220/240V)
Note (1) The data are measured at following conditions
Ambient air temperature
Indoor side: 27°C DB, 19°C WB
Outdoor side: 35°C DB, 24°C WB
Temp. difference between
suction air and discharge
air (˚C)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SRK50A and is the answer not in the manual?

Mitsubishi SRK50A Specifications

General IconGeneral
BrandMitsubishi
ModelSRK50A
CategoryAir Conditioner
LanguageEnglish

Related product manuals