OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0
0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0
0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0
Input correction factors
The operational frequency of compressor
Correction of Cooling total input
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0
Input correction factors
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.5
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0
0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
SUZ-KA25VA(H)
SUZ-KA35VA(H) SUZ-KA35VA(H) SUZ-KA35VA(H) SUZ-KA35VA(H)
SUZ-KA25VA(H) SUZ-KA25VA(H) SUZ-KA25VA(H)
SUZ-KA50VA SUZ-KA50VA SUZ-KA50VA SUZ-KA50VA
<How to operate fixed-frequency operation (Test run operation)>
1. Press the EMERGENCY OPERATION switch or the Test button to COOL or HEAT mode.
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor starts at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts.
6. To cancel test run operation (EMERGENCY OPERATION), press the EMERGENCY OPERATION switch or the ON/OFF
button on remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm
2
[Gauge])
20.8
19.2
17.6
16.0
14.4
12.8
11.2
9.6
23.9
22.1
20.2
18.4
16.5
14.7
12.9
11.0
Indoor air Dry-bulb temperature
difference (degree)
Indoor intake air Dry-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Indoor intake air Dry-bulb temperature ()
SUZ-KA25VA(H)
at Rated frequency
SUZ-KA35VA(H)
at Rated frequency
28.2
26.0
23.9
21.7
19.5
17.4
15.2
13.0
SUZ-KA50VA
at Rated frequency
NOTE: The above curves are for the heating operation without any frost.
OC322G