[SUZ-KA25/35VA(H).TH]
Check of open phase
B
Check of intelligent power module
C
How to check inverter/compressor
A
Check the voltage
between terminals.
Check the
compressor.
Disconnect the connector (CN61)
between compressor and the intelligent
power module (IPM).
Check the resistance of the intelligent
power module.
See D “Check of compressor”.
No
See B “Check of open phase”.
See C 'Check of intelligent power module'.
Is the resistance
infinite?
Yes
Replace the inverter P.C.
board.
No
(0~several
")
Yes
Are the voltages
balanced?
Replace the inverter P.C.
board and compressor.
With the connector between compressor and the intelligent power
module disconnected, activate the inverter and check if the inverter
is normal by measuring the balance of voltage between terminals.
<< Operation method>>
Start cooling or heating operation by pressing the EMERGENCY OPERATION switch
on the indoor unit. (test-run mode : refer to page 31 for SLZ/SUZ and 37 for SEZ/SUZ.)
<<Measurement point>> + Measure AC voltage between the lead wires at 3 points.
BLK (U)-WHT (V)
BLK (U)-RED (W)
WHT(V)-RED (W)
NOTE 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board flashes 9 times.
Measure the resistance between terminals on the intelligent
power module.
<<Measurement point>>
at 6 points
BLK-WHT, WHT-BLK
BLK-RED, RED-BLK
WHT-RED, RED-WHT
<<Judgement>>
Infinite []···········Normal
0~dozens of ······Abnormal (short)
Output voltage [V]
115V
ohmmeter indication
Normal
(infinite)
Abnormal
(0~dozens of )
X1
X1
LED
Inverter P.C. board
9-time flash
2.5-second OFF
Flashing
12-5. Troubleshooting flow
Outdoor unit does not operate.
OC322G