66
LED1 (Red)
LED2 (Yellow)
Lightning Twice Outdoor power system
• Check the connection of the compressor
connecting wire.
•
Refer to 12-5.( "How to check inverter/
compressor".
• Check the stop valve.
Lightning 3 times
Discharge temperature
thermistor
• Refer to 12-5.
) "Check of outdoor thermistor".
• Refer to 12-5.
) "Check of outdoor thermistor".
Outdoor heat exchanger
temperature thermistor
Defrost thermistor
Lightning 7 times Nonvolatile memory data
• Replace the outdoor electronic control P.C. board.
Lightning 8 times Current sensor • Replace the power board.
Lightning 11 times
Communication error
between P.C. boards
• Check the connecting wire between outdoor
electronic control P.C. board and power board.
Lightning 12 times
Zero cross detecting
circuit
• Check the connecting wire among outdoor
electronic control P.C. board, noise filter P.C.
board and power board.
Abnormal point/Condition Correspondence
When a short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 5 minutes
(in cooling) and 10 minutes (in heating) of compressor start-up.
When a short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 5 minutes of
compressor start-up.
• Refer to 12-5.
) "Check of outdoor thermistor".
• Replace the outdoor electronic control P.C.
board.
Indication
When IPM protection stop or lock protection stop is continuously
performed three times within 1 minute after the compressor gets
started, or when converter protection stop or bus-bar voltage
protection stop is continuously performed three times within 3 minutes
after start-up.
When a short circuit is detected in the thermistor during operation, or
when an open circuit is detected in the thermistor after 10 minutes
of compressor start-up.
Condition
When the nonvolatile memory data cannot be read properly.
Lightning 6 times Serial signal
Fin temperature thermistor
P.C board temperature
thermistor
Lightning 4 times
Ambient temperature
thermistor
Current sensor protection stop is continuously performed twice.
When the communication protection stop between boards is
continuously performed twice.
The protection stop of the zero cross detecting circuit is
continuously performed 10 times.
When a short or open circuit is detected in the thermistor
during operation.
When a short or open circuit is detected in the thermistor
during operation.
5 timesLightning
Outdoor electronic control P.C. board (Parts side)
Lighting
IPM protection
Lock protection
3 times Goes out
Discharge temperature
protection
• Check the amount of gas and refrigerant circuit.
• Refer to 12-5.
'"Check of LEV".
Fin temperature protection
P.C. board temperature
protection
High-pressure protection
8 times
Goes out Converter protection
• Replace the power board.
Bus-bar voltage
protection (1)
• Replace the power board.
Bus-bar voltage
protection (2)
13 times Goes out Outdoor fan motor • Refer to 12-5.
* "Check of outdoor fan motor".
Lighting 8 times
Current sensor protection
• Replace the power board.
Lighting 11 times
Communication between
P.C. boards protection
• Check the connecting wire between outdoor
electronic control P.C. board and power board.
Lighting 12 times
Zero cross detecting
circuit protection
• Check the connecting wire among outdoor
electronic control P.C. board, noise filter
P.C. board and power board.
• Check refrigerant circuit and refrigerant amount.
• Refer to 12-5.
' "Check of LEV".
• Check around of gas and the refrigerant circuit.
• Check of stop valve.
• Reconnect compressor connector.
• Refer to 12-5.( "How to check inverter/
compressor".
• Check the stop valve.
• Check the power module (PAM module).
Twice Goes out
4 times Goes out
5 times Goes out
9 times Goes out
When over-current is detected after 30 seconds of compressor
start-up.
When over-current is detected within 30
seconds
of
compressor start-up.
When the bus-bar voltage exceeds 400V or falls to 200V or below
during compressor operating.
When the bus-bar voltage exceeds 400V or falls to 50V or below
during compressor operating.
When temperature of discharge temperature thermistor exceeds 116:,
compressor stops. Compressor can restart if discharge temperature
thermistor reads 100 or less 3 minutes later.
When the fin temperature exceeds 87 during operation.
When the P.C. board temperature exceeds 70 during operation.
When high-pressure is detected with the high-pressure switch (HPS)
during operation.
When failure occurs continuously three times within 30 seconds after
the fan gets started.
When a short or open circuit is detected in the current sensor during
compressor operating.
Communication error occurs between the outdoor electronic control
P.C. board and power board for more than 10 seconds.
When zero cross signal cannot be detected while the compressor is
operating.
When the outdoor heat exchanger temperature exceeds 70 during
cooling or when indoor gas pipe temperature exceeds 70during
heating.
When a failure is detected in the operation of the converter
during operation.
Outdoor unit
does not
operate.
LED2
LED1
Refer to 12-5.% "How to check mis-wiring and
serial signal error".
When the communication fails between the indoor and outdoor unit
for 3 minutes.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit
stops and
restarts 3
minutes later'
is repeated.
SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA (Except for SUZ-KA50VAR2.TH)
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure.
2. LED is lighted during normal operation.