No. Description Setting
010
Heating system
Sets the existing heating system:
• Floor heating, standard (FBH St.)
• Floor heating, low energy (FBH NE)
• Radiator (RAD)
• Convector, passive (KON pas)
• Convector, active (KON akt)
0 = FBH St.
1 = FBH NE
2 = RAD
3 = KON pas
4 = KON akt
Standard: 0
020
Blocking of cooling
Deactivates the cooling function.
0 = activated
1 = deactivated
Standard: 0
030
Operating lock
Protects the deactivation of the operating
lock with a PIN.
0 = deactivated
1 = activated
Standard: 0
031
PIN operating lock
Sets the PIN for parameter 30.
0 ... 9999
Standard: 0000
040
External sensor (only Control)
Registration of an external room sensor or
floor sensor. The registration of a room sen-
sor deactivates the internal sensor. If a floor
sensor is used, the minimum floor tempera-
ture can be set via the Settings menu in the
function “External floor sensor”.
0 = no external
sensor
1 = room sensor
2 = floor sensor
Standard: 0
041
Correction of actual temperature of
external sensor
(only Control)
Corrects a deviating measurement of the ac-
tual temperature.
-2 ... +2°C
Standard: 0 °C
050
Duration of the display illumination
Sets the duration of further illumination of
the display after use.
0 ... 30sec.
in 5 second incre-
ments
Standard: 15sec.
Service menu