6 Maintenance
6.1 Troubleshooting
Display Meaning Possible elimination
Measuring
temperature of
internal/external
sensor exceeded
Internal sensor/room sensor
Remove external heat sources in the
direct environment and wait until
the sensor has cooled down again.
Reposition the room sensor if
necessary.
Have the room thermostat/room
sensor checked and replaced if
necessary.
Floor sensor
Have the floor sensor checked and
replaced if necessary.
0004 Malfunction in
external sensor
(room/floor
sensor)
No external sensor connected.
Reset to the factory settings.
Deactivate the external sensor in
the Service menu under parameter
040.
Have the external checked and
replaced if necessary.
0010 Malfunction in
internal sensor
Reset to the factory settings.
Have the room thermostat checked
and replaced if necessary.