02/12/16 CH7K20C1_IT-EN-DE
ENGLISH
ENGLISH
11. CONTROLLER INFORMATION SCREEN
OFFMAN AUT TEST !
Not ready
MainsFlt
PF 0.00
RPM 0
No Timer
0 kW 0
InteliLite NT
ComAp 2007-2008
Page
Languages
>English
Chinese
Enter + Page
IL-NT-x.y
Serial:12345678
SW ver: x.y, x.y
Appl : AMF25
Branch: Standard
User
User interface:
>Engineer
Page
Page
Serial: 12345678
Pwd. dec.: 1234567890
Enter
Enter
CONTROLLER AMF25
12. PROCEDURE FOR HOUR/MAINTENANCE ALERT RESET
POSITION BUTTON DESCRIPTION
1
Enter the Password as you can see in Section 9.
(if the password wasn’t changed before is 25)
2
When you ave entered the password press PAGE.
3
Press ↓ to select ENGINE PROTECT and press ENTER.
4
Press ↓ to select WRN MAINTENANCE and press ENTER.
5
Press
↑ to set up hours for the next maintenance operation.
(You have to set up hours following the instruction of user manual or the direction of the
maintener)
6
Press PAGE 3 times to go back to the Home Page.
REV.1-07-19