1 digital relay output to alarm (normal
close
): current carrying capacity 1 A @ 30
UL/cUL Class 1 Division 2 Group A/B/C/D,
ATEX Zone 2, IECEx
This device complies with Part 15 of the FCC rules.
Operation is subject to the following conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interference that may cause undesired operation.
ATEX and IECEx Information
DEMKO Certification number: 07 ATEX 0690059X IEC Certification
Number: IECEx UL 13.0023X (only for models with suffix –CT or –
Ambient Temperature Range (-40°C ≤ Tamb ≤ 75°C)
3.
Certification String: Ex nA IIC T3 Gc
Standards Covered: EN 60079-0:2012/IEC 60079-
60079-15:2010/IEC 60079-15 4th Ed.
The conditions of safe usage:
•
The Ethernet Communications Devices are intended for mounting
in a tool-accessible IP54 enclosure and used in an area of not
more than pollution degree 2 as defined by IEC 60664-1.
• Conductors suitable for use in an ambient temperature greater
than 114°C must be used for the power supply terminal.
• A 4mm2 conductor must be used when connection to
grounding screw is utilized.
•
Provisions shall be made, either in the equipment or external to
the equipment, to prevent the peak rated voltage being exceeded
by the transient disturbances of more than 140%.