STANDARD
DUAL DISPLAY
PID AUTOTUNE
RAMP-TO-SETPOINT
UL
C, UL, CE (4810)
AUTO / MANUAL
15 SECURITY OPTIONS
UNIVERSAL INPUT
OPTIONS
DUAL OUTPUT
ALARMS - 15 TYPES
24VDC EXCITATION
Rs485 COMMUNICATIONS
SPECIFICATIONS
1. INPUT
*Thermocouple J, K, T, E, B, R, S, N ( IPTS68/DIN 43710)
*RTD Pt100 ohms RTD (DIN 43760/BS 1904 or JIS)
*Linear Voltage (current) -10 to 60 mV confugurablewith input attenuation
*Range User configurable
*Accuracy +/-2C for T/C, _+0.2C for RTD, _+0.05% for Linear input.
*Cold Junction Compenasation 0.1% ambient typical.
*Input Impedance 10M ohms for T/C, 100K ohms for Linear Voltage,
2.7 Ohms for 0 (4)- 20 mA/
*Excitation Current for RTD 0.2mA Max.
*Sample Rate 250mS
2. CONTROL
*Proportional Band 0.0-100.0%
*Rest (Integral) 0-3600 Sec.
*Rate (Derivative) 0-3600 Sec.
*Anti Rest Windup Inhibit integral action outside Proportion Band
*Ramp Rate 0.0-100.0C / minute.
*Dwell minutes.
*On-Off With adjustable hysteresis
*Cycle Time 0-99 seconds.
*Control Action Configurable for Direct (cooling) or Reverse (Heating)
3. OUTPUT
*Relay 5A/240VAC resistive.
*Pulsed Voltage Isloated 24 VDC 100mA Max.
*Current Isolated 0 (4) - 20 mA Max load 500 ohms.
*Alarm Relay output, (SPST) 10A/240VAC resistive.
4. POWER
*Rating 85 - 265 VAC 50/60Hz 5VA max
5. ENVIRONMENTAL
*Operating Temp -10 - 50C
*Humidity - 90%
*Insulation 20M ohms minimum @ 500VDC
*EMC Emission EN500081-1:1992, EN55022:1994
*EMC Immunity EN 50082-1:1992, IEC 801-3, IEC 801-4:1988
*Weight VT4810 180g, VT4910 240g, VT9610 240g
SCALE____________________
NOTE: Vt4810 - EITHER OUT2 or ALM1
TEMPERATEMPERA
TEMPERATEMPERA
TEMPERA
TURE CONTRTURE CONTR
TURE CONTRTURE CONTR
TURE CONTR
OLSOLS
OLSOLS
OLS
VT10 SERIESVT10 SERIES
VT10 SERIESVT10 SERIES
VT10 SERIES
pg.1
Question and Answer IconNeed help?

Do you have a question about the MPI VT10 Series and is the answer not in the manual?

Summary

Specifications

Input Specifications

Details supported input types (Thermocouple, RTD, Linear Voltage), ranges, accuracy, and impedance.

Control Specifications

Covers PID parameters like Proportional Band, Integral Time, Derivative Time, and control action.

Output Specifications

Describes available output types (Relay, Pulsed Voltage, Current) and their ratings.

Parameter Configuration Flowchart

Parameter Reference Guide

Level 1 Parameters

Details parameters like Setpoint Ramp, Output Offset, Alarm Setpoints, and Delay Times.

Level 2 Parameters

Covers Proportional Band, Integral Time, Derivative Time, and Deadband for outputs.

Configuration Details

Troubleshooting

Error Messages and Solutions

Provides a guide for common error symbols and their corresponding solutions for troubleshooting.

Calibration Procedure

Calibration Warning and Preparation

Emphasizes the need for proper equipment and trained personnel before starting calibration.

Low and High Point Calibration

Guides through the steps for calibrating the controller's input signals at low and high points.

MPI VT10 Series Specifications

General IconGeneral
Control AlgorithmPID, On/Off
Power Supply100-240 VAC, 24 VDC
Input TypeThermocouple, RTD
Control OutputRelay, SSR
DisplayLED
CommunicationRS485 (optional)
Operating Temperature0 to 50°C
Dimensions96x96x100mm