3
rd
party Lithium battery
If selected, programs of 02, 26,
27 and 29 will be automatically
set up. No need for further
setting. Please contact the
battery supplier for installation
procedure.
Auto restart when overload
occurs
Restart disable (default)
Auto restart when over
temperature occurs
Restart disable (default)
Maximum utility charging
current
Note: If setting value in
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02
for utility charger.
Setting range is from 2A, then 10A to 120A. Increment of each
click is 10A.
Setting voltage point back
to utility source when
selecting “SBU” (SBU
priority) in program 01.
Setting range is from 44V to 51V.
Increment of each click is 1V.