Troubleshooting 46
8.13 PC 02 (Top temperature protection of compressor diagnosis and solution)
Description: If the sampling voltage is not 5V, the LED will display the failure.
Recommended parts to prepare:
Connection wires
Overload protector
Outdoor PCB
Troubleshooting and repair:
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the temperature of
compressor Top
Is more than 90℃?
No
Check if the refrigerant
system
is normal?
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB.Yes
No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the MrCool DIY-MULTI4-36HP230C and is the answer not in the manual?

MrCool DIY-MULTI4-36HP230C Specifications

General IconGeneral
BrandMrCool
ModelDIY-MULTI4-36HP230C
CategoryAir Conditioner
LanguageEnglish

Related product manuals