507769C05Page 18 of 55
mrcool.com
Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 0 - 2,000 ft
Number of
90° Elbows
Used
1-1/2” Pipe 2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity Capacity
045 070 090 110 045 070 090 110 045 070 090 110 045 070 090 110
1 10 10
n/a n/a
53 38 22
n/a
90 70 39
n/a
111 111 104 104
2
n/a n/a
48 33 17 85 65 34 106 106 99 99
3 43 28 12 80 60 29 101 101 94 94
4 38 23
n/a
75 55 24 96 96 89 89
5 33 18 70 50 19 91 91 84 84
6 28 13 65 45 14 86 86 79 79
7 23 60 40 9 81 81 74 74
8 18 55 35
n/a
76 76 69 69
9 13 50 30 71 71 64 64
10 n/a 45 25 66 66 59 59
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
Table 7C.
Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 2,001 - 10,000 ft
Number of 90°
Elbows Used
2” Pipe 2-1/2" Pipe 3" Pipe
Capacity Capacity Capacity
045 070 090 110
030/
045
070 090 110
030/
045
070 090 110
1 35 25 15
n/a
90 63 39
n/a
111 111 104 104
2 30 20 10 85 58 34 106 106 99 99
3 25 15
n/a
80 53 29 101 101 94 94
4 20 10 75 48 24 96 96 89 89
5 15
n/a
70 43 19 91 91 84 84
6 10 65 38 14 86 86 79 79
7
n/a
60 33 9 81 81 74 74
8 55 28
n/a
76 76 69 69
9 50 23 71 71 64 64
10 45 18 66 66 59 59
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.