OPERATING AND MAINTENANCE MANUAL
Chapter 7 - Electronic controller
TAEevo Tech 015÷802 60 Hz UL
99
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
EN
ENGLISH
FS43 C Ambient air set point for condensing fans forcing to maximum
speed
-50
-58
110.0
230
°C
°F
FS44 C Ambient air differential for condensing fans forcing to maximum
speed
0.1
0
25.0
45
°C
°F
FS45 C Condensing fans control delay time in free cooling 0 250 Min
FS46 C Anti-Legionella cycle operation type:
0= Compressors and heaters
1= First compressors and then heaters
2= Heaters only
3= Compressors only
03
FS47 C Disabling of evaporator pump in domestic hot water production:
0= Enabled
1= Disabled
01
FS48 C Selection of probe for forced exit from domestic hot water
production:
0= Function disabled
1= Probe Pb1
2= Probe Pb2
...
020
FS49 C Start domestic hot water temperature control:
0= On request of all steps
1= On request of first step
01
FS50 C Compressors deactivation setpoint during Anti-Legionella cycle -50
-58
110.0
230
°C
°F
FS51 C Safety time of compressor in case of domestic hot water request:
0= Safety times not observed
1= Safety times observed
01
FS52 C Domestic hot water low temperature setpoint -50
-58
110.0
230
°C
°F
FS53 C Domestic hot water low temperature proportional band 0.1
0
25.0
45
°C
°F
FS54 C Selection of probe for low temperature control of domestic hot
water:
0= Not used
1= Pb1
2= Pb2
....
020
FS55 C Enabling of solar panels in heating / integration with domestic hot
water production:
0= Not enabled
1= Integration
2= Heating
02
FS56 C Enabling of solar panels in heating or integration with heating:
0= Not enabled
1= Integration
2= Heating
02
FS57 C Selection of probe for solar panels Dt in domestic hot water
production
020
FS58 C Selection of probe for solar panels Dt in heating 0 20
FS59 C Solar panels enabling Dt in domestic hot water production 0.1
0
25.0
45
°C
°F
Dec
Int
FS60 C Solar panels enabling Dt in heating 0.1
0
25.0
45
°C
°F
Dec
Int
FS61 C Solar panels maximum time if set is not satisfied 0 250 Min
FS62 C Selection of probe for Free cooling end due to low temperature 0 20
FS63 C Free cooling end setpoint due to low temperature -50
-58
110
230
°C
°F
FS64 C Free cooling end differential due to low temperature 0.1
0
25.0
45
°C
°F
Pr1 U User password 0 999
Pr2 S Service password 0 999
Parameter Level Description Min. Max. UM Resolution