AL42 C Maximum number of trips per hour of generic unit shut-down
alarm.
Establishes a maximum number of trips per hour of the generic
unit shut-down alarm, after which the alarm switches from
automatic reset to manual reset.
Reset is always manual if AL42=0.
Reset is always automatic if AL42=16.
Reset switches from automatic to manual if AL42 is from 1 to 15.
0 16
AL43 C Generic unit shut-down alarm delay time with digital input active. 0 250 Sec
AL44 C Generic unit shut-down alarm delay time with digital input
inactive.
0 250 10 Sec 10 Sec
Alarm relay
AL45 C Enables alarm relay output in remote OFF or stand-by:
0= Alarm output enabled
1= Alarm output disabled
01
Alarms log - compressors thermal alarm reset password
AL46 C Value of alarms log, compressors thermal alarm and anti-freeze
alarm reset password (refer to procedures)
0 999
AL47 C Operation of compressor thermal alarm:
0= Blocks single compressor
1= Blocks circuit
01
AL48 C Compressor thermal alarm with compressor in OFF:
0= Alarm acknowledgement disabled
1= Alarm acknowledgement enabled
01
Compressor oil alarm management
AL49 C Oil level sensor / level float alarm with compressor in OFF:
0= Alarm acknowledgement disabled
1= Alarm acknowledgement enabled
01
Unit generic block / signalling alarm no. 2
AL50 C Generic alarm no. 2 operation:
0= Display- only not dependent on AL51 (alarm relay and buzzer
activated) always automatic reset
1= the alarm blocks the unit; the alarm reset depends on the value
of parameter AL51
01
AL51 C Maximum number of trips per hour of generic unit shut-down
alarm no. 2. Establishes a maximum number of trips per hour of
the generic unit shut-down alarm, after which the alarm switches
from automatic reset to manual reset
Reset is always manual if AL51=0
Reset is always automatic if AL51=16
Reset switches from automatic to manual if AL51 is from 1 to 15
116
AL52 C Generic unit shut-down alarm delay time with digital input active 0 250 Sec Sec
AL53 C Generic unit shut-down alarm delay time with digital input
inactive
0 250 Sec Sec
High pressure alarm reset
AL54 C Maximum number of trips per hour of high condensing
temperature / pressure alarm from digital / analogue input. Reset
is always manual if AL54=0
Reset is always automatic if AL54=16
Reset switches from automatic to manual if AL54 is from 1 to 15
016
Condenser side water pump flow switch alarm
AL55 C Condenser flow switch alarm delay from starting of condenser
water pump
0 250 Sec 0
AL56 C Maximum holding time of condenser flow switch alarm before
switching to manual and blocking the condenser water pump, if it
is running
0 250 Sec 0
AL57 C Condenser flow switch input active duration 0 250 Sec 0
AL58 C Condenser flow switch input inactive duration 0 250 Sec 0
Evaporator water inlet high temperature alarm
Parameter Level Description Min. Max. UM Resolution