OPERATING AND MAINTENANCE MANUAL
Chapter 7 - Electronic controller
TAEevo Tech 015÷802 60 Hz UL
104
The data in this manual are not binding and they can be modified by the manufacturer without notice. Reproduction of this manual is strictly prohibited
ENGLISH
EN
AL59 C Max. number of trips per hour of system water inlet high
temperature probe alarm
Reset is always manual if AL59=0
Reset is always automatic if AL59=16
Reset switches from automatic to manual if AL59 is from 1 to 15
016
AL60 C Plant water inlet high temperature probe alarm delay from
compressor ON
0 250 Sec 10 Sec
AL61 C Plant water inlet high temperature probe alarm setpoint -50.0
-58
110
230
°C
°F
Dec
Int
AL62 C Plant water inlet high temperature probe alarm differential 0.1
0
25.0
45
°C
°F
Dec
Int
AL63 C Configuration of NTC / PTC analogue input for management of
the system water inlet high temperature alarm:
0= Function disabled
020
AL64 C Low pressure alarm signalling delay from digital input activation 0 250 Sec
Domestic hot water pump flow switch alarm
AL65 C Domestic hot water pump flow switch alarm delay 0 250 Sec
AL66 C Domestic hot water pump flow switch manual alarm delay 0 250 Sec
AL67 C Domestic hot water pump flow switch input active duration 0 250 Sec
AL68 C Domestic hot water pump flow switch input inactive duration 0 250 Sec
Solar panels water pump flow switch alarm
AL69 C Solar panels flow switch alarm delay 0 250 Sec
AL70 C Solar panels flow switch manual alarm delay 0 250 Sec
AL71 C Solar panels pump flow switch input active duration 0 250 Sec
AL72 C Solar panels pump flow switch input inactive duration 0 250 Sec
Domestic hot water heater thermal alarm
AL73 C Maximum number of trips per hour of the domestic hot water
heater thermal alarm. Reset is always manual if AL73=0
Reset is always automatic if AL73=16
Reset switches from automatic to manual if AL73 is from 1 to 15
016
Selection of the anti-freeze alarm reset type
AL74 C Manual reset anti-freeze alarm with password required:
0= Password not required
1= Password required
01
Domestic hot water pump thermal alarm
AL75 C Maximum number of trips per hour of the domestic hot water
pump thermal alarm. Reset is always manual if AL75=0
Reset is always automatic if AL75=16
Reset switches from automatic to manual if AL75 is from 1 to 15
016
Compressor oil alarm
AL76 C Compressor oil alarm as display only:
0= Automatic reset or manual oil alarm (AL13) with compressor
block
1= Compressor oil alarm as display only
01
Compressor thermal alarm
AL77 C Automatic reset compressor thermal alarm:
0= Always manual reset compressor thermal alarm
1= Automatic reset compressor thermal alarm
01
AL78 C Dt for compressor or circuit oil differential alarm 0.1
1
14.0
203
Bar
Psi
Dec
Int
AL79 C Differential for compressor or circuit oil differential alarm reset 0.1
1
14.0
203
Bar
Psi
Dec
Int
AL80 C Maximum number of trips per hour of compressor oil differential
alarm
Reset is always manual if AL73=0.
Reset is always automatic if AL73=16
Reset switches from automatic to manual if AL73 is from 1 to 15
016
Parameter Level Description Min. Max. UM Resolution