What to do if the MTE RL Industrial Electrical filter output voltage is not within specification?
- MMr. Dalton MasonJul 28, 2025
If the filter output voltage isn't within the specified range, several factors could be at play. First, check that the reactor input voltage is within its specified tolerance, referring to the reactor service conditions and performance specifications. Also, verify that the source impedance is within the acceptable range, again consulting the reactor's specifications. The drive setup parameter might not be configured for an input reactor, so you should consult the drive manufacturer to update the setup. Finally, extreme voltage transients, like switching between voltage sources, can cause issues. Avoid source switching without proper phase synchronizing or a reasonable time delay.