Page 4
bags, clearly labelled as RCF waste and may be disposed of in suitably licensed landfill
sites.
It should be noted that exposure to the fibres is unlikely in normal use.
2.1. Flue Specifications
All appliance sizes have been tested and approved with a flue of 7” (178mm) diameter and
having a minimum effective height of 10ft (3m).
2.2. Ventilation Requirements
The room in which the appliance is to be fitted must have permanent air vent with
a minimum effective area of 100 sq. cm (15
1/2
sq. inches) and be accessible to
the outside air.
All ventilation must comply with the rules in force for the country in which
the appliance is fitted.
NOTE: Vent should be checked on a regular basis to ensure that there is no obstruction.
Warning
An extractor fan must not be fitted in the room that the ventilation is
taken from.