24 Installing the System Piping
3.1.3 Space Heating System Piping
When connecting the space heating system, follow these guidelines:
Ɣ
Carefully tighten all connections to avoid damage to fittings.
Ɣ
After installing the boiler, check the space heating system's operation and inspect for leaks.
Pump Specifications
Model Temp. Rise
Pump Model
Grundfos Taco Bell & Gossett Armstrong
NFB-301C
20°F UPS26-150 2400-60 NRF-36 E8.2
25°F UPS26-150 0013 NRF-36 E7.2
35°F UPS26-99 0010 NRF-36 E7.2
NFB-399C
20°F UPS26-150 2400-60 NRF-45 E11.2
25°F UPS26-150 0013 NRF-45 E8.2
35°F UPS26-99 0010 NRF-36 E7.2
Note
If you are not using one of the pumps listed in the above tables, use a pump with an integral check valve or install a check valve at
the pump outlet. Refer to the performance curve on page 25 to select a pump that suits your application. The dry contacts on
the boiler can supply up to a maximum of 5A current at the boiler pump connection terminal.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NHB Series and is the answer not in the manual?

Navien NHB Series Specifications

General IconGeneral
TypeCondensing Boiler
EfficiencyUp to 95% AFUE
Fuel TypeNatural Gas or Propane
Vent TypeDirect Vent
Vent Diameter2" or 3"
Heat Exchanger MaterialStainless Steel
Water Connections3/4" NPT
DimensionsVaries by model
WeightVaries by model
Warranty5-Year Parts