4 Installation Area
Figure 4.1 shows the required installation area.
Be sure to provide a work area as shown below in order to connect cables and perform necessary
maintenance of installed equipment.
- At least 1.0 m in the front and rear of the rack
- At least 0.6 m to the left and right of the rack (when racks are coupled, to the left and right of the coupled
unit)
- At least 0.4 m from the top of the rack to the ceiling
Figure 4.1 Installation Area
1.0 m
0.6 m
0.4 m from
top of rack to
ceiling
0.6 m
1.0 m