Basis AB 4071-12
INHALT
Übersicht .....................................2
Produktbeschreibung ..............2
Lieferumfang ...........................2
Optionales Zubehör ...............2
Systembeschreibung ...............3
Infosymbole .............................3
Das System Funk 868 MHz ......3
Heizen/Kühlen-Funktion .........4
Sicherheit ....................................4
Sicherheitshinweise .................4
Montageanleitung .....................5
Montage auf Tragschiene .......5
Anschluss der Antriebe ...........5
Betriebsanleitung .......................6
Inbetriebnahme .......................6
Energiesparprogramme ..........6
Heizzonen zuordnen ...............7
Funktionstests ..........................7
Installation Regler Funk ..........8
Regelbetrieb ............................8
Signalisierung der Heizzonen (HZ) .....9
Löschen aller Einstellungen ....9
Austauschen der Sicherung ....9
Technische Daten .....................10
Technische Daten ...................10
Störbeseitigung .....................11
Anhang .....................................12
Systemübersicht .....................12
Urheberrecht .........................12
Basis AB 4071-6
HANDBUCH
Alpha-Basis Funk 868 MHz
8-D51-53-017 Rev 1.0

Table of Contents

Questions and Answers

  • S
    Shawn PhillipsJul 25, 2025
    What to do if the Neotherm Control Unit fuse is defective but the indicator lights up?
    • K
      Katrina WestJul 25, 2025
      If the fuse is defective but the indicator lights up, it could be due to a short circuit in the individual room control. To resolve this, shut off the unit, disconnect the actuators (observing the correct order), and insert a new fuse. If the fuse no longer trips, inspect the actuators for damage and the valves for leaks, replacing any defective parts as needed. If the fuse trips repeatedly, examine the connected thermostats for faulty wiring.
  • L
    lanebrianAug 10, 2025
    Why is the operation indicator not lighting up on my Neotherm Basis AB 4071-12 Control Unit?
    • J
      Jonathan AndersonAug 11, 2025
      If the operation indicator on your Neotherm Control Unit is not lighting up, there are a couple of potential causes. First, there may be a wiring error in the main connection, so check the wiring. Second, there might be no main voltage present, so check the supply circuit fuse.

Summary

Overview

Product Description

Detailed description of the Alpha-Basis Funk 868 MHz system's features and components.

System Description

Heating;Cooling Functionality

Safety Information

Safety Notes and Hazards

Covers intended use, safety warnings, authorized personnel, and potential hazards.

Installation Guide

Mounting and Actuator Connection

Guides on how to mount the unit and connect actuators to heating circuit valves.

Operating Procedures

Start-up and Energy Saving Programs

Instructions for initial system start-up and configuring energy-saving programs.

Configuration and Testing

Allocating Heating Zones

Step-by-step process for assigning wireless thermostats to heating zones.

Thermostat Setup and Control

Technical Specifications

Troubleshooting Guide

Malfunction Diagnosis and Resolution

Lists common malfunctions, their causes, and suggested elimination steps.

Neotherm Basis AB 4071-12 Specifications

General IconGeneral
BrandNeotherm
ModelBasis AB 4071-12
CategoryControl Unit
LanguageEnglish