EasyManua.ls Logo

Nexa FS-558/RF - User Manual

Nexa FS-558/RF
2 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
TECHNICAL DATA
Power source
DC 2 x 1.5V AA battery
Battery: Gold Peak Group: GP 15A LR6 or Energizer: E91
Radio frequency
433 MHz
Range, clear line of sight
up to 20 m
Alarm signal
85 dB (A) at 3 metres
Operating temperature
5°C – 45°C
Ambient humidity
10 – 90 %
Temperature sensors
54-70 °C (EN-54)
This instruction folder contains important information
on correct installation and maintenance of your smoke
alarm. Read through the whole folder before installing
it, and keep the folder for future reference.
Nexa’s FS-588/RF smoke alarm is designed to detect
smoke particles. It has a built-in temperature sensor to
provide an early warning in the event of a fire (as long
as it is positioned and maintained correctly).
Primary features:
Built-in temperature warning device
High levels of sensitivity and stability
Test and pause functions
LED shows normal function
Signal on low battery voltage
Can be connected in series with up to 12 smoke alarms
IMPORTANT
The radio range may vary depending on the location, the
design of the building and the materials used in the building.
Do not remove or disconnect the batteries to stop false
alarms as this will disable the vital function of the smoke
alarm. Open windows or ventilate the air around the smoke
alarm in order to stop it, and/or press the pause button.
The smoke alarm is intended for use for use in single-
family homes. In multiple-occupancy buildings, each
home must be equipped with its own smoke alarms.
This smoke alarm is not suitable for use in buildings that
are not used for residential purposes. The smoke alarm
is no substitute for a full alarm system that is required
by law or by the fire authorities.
The smoke alarm detects combustion particles in the air
(smoke). It does not react to flames or gas.
The smoke alarm is designed to emit an alarm signal if a
fire is developing.
The smoke alarm should be tested every week and
replaced every ten years.
POSITIONING THE SMOKE ALARM
For the smoke alarm to provide an early warning, it has to
be installed in the location where the re starts. Therefore,
Nexa recommends that you install smoke alarms in each
room and on all oors.
Single-level home: To achieve minimum protection,
position the alarm in the entrance hall between the living
areas (including the kitchen) and the sleeping areas.
Position it as close as possible to the living areas, and
make sure the alarm can be heard by anyone in the
bedrooms. See Figure 1, for example:
Multi-storey home: To achieve minimum protection,
position and alarm in the stairwell (at ground level) and
another alarm above the landing on the top oor, as well
as an alarm on the ceiling in the basement at the foot of
the stairs. This covers the basement level, but not crawl
spaces and unfurnished attics.
See the example in Figure 2.
Ceiling installation
Hot smoke rises and spreads, so installing your smoke alarm in
a central location on the ceiling is recommended. Avoid areas
where air does not circulate, e.g. corners. Also keep it away
from objects that may prevent the free ow of air. Position the
device at least 30 cm from light ttings or interior ttings that
may prevent smoke/heat reaching the detector. Position it at
least 1 metre away from the wall.
See Figure 3A.
Wall mounting, if ceiling mounting is not possible
Avoid installing the device a long way into a corner.
Position the upper edge of the smoke alarm at least 15 cm and
no more than 30 cm away from the ceiling. See Figure 3A.
Sloping ceilings
In the case of sloping surfaces or ceilings that move up
towards a ridge, the detector must be installed 90 cm from
the highest point, measured horizontally, because still air
under the ridge may prevent smoke reaching the device.
See Figure 3B.
NOTE: There must be an alarm in every room (except the
kitchen, bathroom and garage) to provide recommended/
maximum protection. DO NOT POSITION AN ALARM IN THE
KITCHEN or BATHROOM as cooking smells or steam may
activate the alarm. DO NOT POSITION AN ALARM IN THE
GARAGE as there is a risk of it being triggered by exhaust fumes.
INSTALLATION
1. Remove the mounting plate on the back of the
smoke alarm by rotating the mounting plate
counterclockwise.
2. Insert 2 x AA / LR6 batteries. Make sure you are using
the correct polarity (+/-).
3. Test and programme the smoke alarm – see the
sections TESTING and PROGRAMMING.
4. Install the mounting plate in a selected location on the
ceiling. Take care when positioning your smoke alarm.
5. Place the smoke alarm on the mounting plate and rotate
the smoke alarm clockwise until it clicks into place.
6. Press the test button to check that smoke alarm is
working correctly.
TESTING
Test your smoke alarms by pressing the test button. Your
smoke alarm will respond by emitting an alarm signal.
Test your alarms both before and after installation so
as to be sure that they are working.
Only test your alarms using the test button. Never use
a naked ame as this may destroy the smoke alarm.
Get into the habit of testing your smoke alarms once a week.
Testing interlinked alarms: It takes up to 30 seconds
for all interlinked alarms to respond/emit an alarm.
HOLD DOWN THE TEST BUTTON until all smoke
alarms have emitted an alarm.
PROGRAMMING
The FS-558 / RF is equipped with RF transmitter
and receiver to communicate with each other. For
this to work, the re alarms must be connected by
programming.
Select one of the smoke alarms as the master unit and
mark it with an M for ease of recognition.
During programming, the master device sends out radio
code to the other smoke alarms to interconnect them.
1. Press the master unit test button for about 15
seconds until the LED indicator lights up with a solid
light. The master unit is now in programming mode
and ready to hand out radio code the other smoke
alarms. The master unit stays in programming mode
for about 30 seconds before returning to normal
mode.
2. With the master unit in programming mode, press
and hold the slave unit’s test button until the LED
indicator is solidly lit (1-3 seconds), release the
button, and then press it again. Both the master
unit and slave unit LED indicators will now blink
quickly for 2 seconds. This shows that the two are
interconnected.
3. Repeat step 2 with all slave units to be connected to
the same system.
4. Quit programming by pressing the test button on the
master unit so that the LED indicator goes out.
HALL-
WAY
BASEMENT
LIVING ROOM
BATHROOM
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
HALLWAY
Maximum /
recommended
protection
Minimum
protection
CEILING
WALL
BEST IN THE
MIDDLE OF THE ROOM
Min. 1 m
Min.
15 cm
Max.
30 cm
BATHROOM
BEDROOM
90 cm
LIVING
ROOM
LANDING
KITCHEN
HALL-
WAY
BASEMENT
LIVING ROOM
BATHROOM
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
HALLWAY
Maximum /
recommended
protection
Minimum
protection
CEILING
WALL
BEST IN THE
MIDDLE OF THE ROOM
Min. 1 m
Min.
15 cm
Max.
30 cm
BATHROOM
BEDROOM
90 cm
LIVING
ROOM
LANDING
KITCHEN
FIGURE 1. Single-level home
FIGURE 3A FIGURE 3B
FIGURE 2. Multi-storey home
LOCATION ON CEILING AND WALL
OPTICAL SMOKE ALARM FOR
WIRELESS CONNECTION IN SERIES
Model: FS-558/RF

Other manuals for Nexa FS-558/RF

Question and Answer IconNeed help?

Do you have a question about the Nexa FS-558/RF and is the answer not in the manual?

Overview

The Nexa FS-558/RF is an optical smoke alarm designed for wireless connection in series, providing early warning in the event of a fire. It detects smoke particles and features a built-in temperature sensor to enhance its fire detection capabilities. This device is intended for use in single-family homes, with each home in multi-occupancy buildings requiring its own smoke alarms. It is not suitable for non-residential buildings and should not be considered a substitute for a full alarm system required by law. The smoke alarm detects combustion particles but does not react to flames or gas. It is designed to emit an alarm signal when a fire is developing and should be tested weekly and replaced every ten years.

For optimal early warning, Nexa recommends installing smoke alarms in every room and on all floors, excluding kitchens, bathrooms, and garages where cooking smells, steam, or exhaust fumes could trigger false alarms. In a single-level home, the alarm should be positioned in the entrance hall between living and sleeping areas, as close as possible to living areas, and audible in bedrooms. For multi-storey homes, an alarm should be placed in the stairwell at ground level, another above the top floor landing, and one on the ceiling in the basement. These positions cover the basement level but exclude crawl spaces and unfurnished attics.

When installing on a ceiling, the smoke alarm should be in a central location to leverage the rising and spreading nature of hot smoke. Avoid corners or areas where air circulation is poor. The device should be at least 30 cm away from light fittings or interior fixtures that might obstruct smoke or heat, and at least 1 meter away from any wall. If ceiling mounting is not feasible, wall mounting is an option. In this case, the upper edge of the smoke alarm should be at least 15 cm and no more than 30 cm from the ceiling, avoiding deep corners. For sloping ceilings or those leading to a ridge, the detector should be installed 90 cm horizontally from the highest point, as still air under the ridge can prevent smoke from reaching the device.

Installation involves removing the mounting plate by rotating it counterclockwise, inserting two AA/LR6 batteries with correct polarity, and then testing and programming the smoke alarm. The mounting plate is then installed in the chosen location on the ceiling, and the smoke alarm is placed on the plate and rotated clockwise until it clicks into place. A final press of the test button confirms correct operation.

The smoke alarm features a test button for verifying its functionality. It is crucial to test alarms both before and after installation to ensure they are working. Only the test button should be used; never use a naked flame, as this can damage the device. Weekly testing is recommended. For interlinked alarms, hold down the test button until all alarms have emitted a signal, which may take up to 30 seconds.

The FS-558/RF is equipped with RF transmitter and receiver for wireless interconnection. To program the alarms, one unit is designated as the master unit (marked with an 'M' for easy identification). The master unit sends out a radio code to other slave units during programming. To initiate programming, press and hold the master unit's test button for about 15 seconds until its LED indicator lights up solidly. The master unit remains in programming mode for approximately 30 seconds. While the master unit is in programming mode, press and hold a slave unit's test button until its LED lights up solidly (1-3 seconds), then release and press it again. Both master and slave unit LEDs will blink quickly for 2 seconds, confirming interconnection. This process is repeated for all slave units. Programming is exited by pressing the test button on the master unit until its LED indicator goes out.

To delete programming (resetting), press and hold the test button on the device for about 20 seconds until the LED indicator flashes quickly, then release it. The LED will then light up solidly. While the LED is solid, press the test button twice. A short beep confirms successful reset. This process is repeated for all devices to be reset. Due to potential wireless communication interference, weekly testing of fire detectors is important to ensure proper communication between devices.

In normal operation, the smoke alarm's LED flashes every 40 seconds, indicating correct battery and device function. If smoke is detected, a loud, pulsing alarm will sound, and the red LED will flash until the smoke clears. The FS-558/RF emits different audible signals for smoke detection and temperature increases, allowing identification of the trigger. Smoke detection results in three long audible signals followed by a pause, while a temperature increase triggers three short audible signals followed by a pause. Interconnected devices receiving a signal from a triggered alarm will emit two short audible signals followed by a pause.

The smoke alarm features a combined test and pause button. The pause function allows temporary silencing of the alarm for 10 minutes in case of a false alarm. After 10 minutes, the alarm resets to normal sensitivity. If needed, the pause function can be reactivated. For interlinked systems, pressing the test/pause button on the device that triggered the alarm will pause all connected devices.

False alarms can be caused by various factors. Smoke alarms react to smoke particles, but also to dust, moisture, pollen, or insects. To avoid false alarms, position the smoke alarm at least 2 meters away from bathrooms, laundry rooms, or other areas with high ambient humidity. Regular vacuuming of the smoke alarm, using a plastic nozzle to avoid damaging electronics, helps remove dust and dirt. Avoid installing smoke alarms in draughty locations or close to windows, doors, ventilation systems, fans, air ducts, and heat pumps, as these can cause dust particles to enter the detection chamber. Rapid temperature variations, such as those near frequently opened windows or doors, can cause condensation in the detection chamber. Smoke alarms should be placed in locations with consistent and stable temperatures. Incorrect positioning in an unstable indoor environment, close proximity to electrical devices (EMC), and lighting can also lead to false alarms. It is recommended to position smoke alarms at least 5 meters away from fireplaces, stoves, or other heaters, 2 meters from ventilation ducts, heat pumps, and air conditioning, and 1 meter from lamps and fluorescent tubes.

Battery replacement frequency depends on the battery type. It is advisable to replace batteries annually, ideally on a specific date. To replace batteries, rotate the smoke alarm counterclockwise to remove it from the mounting plate, remove old batteries, insert new ones with correct polarity, and then place the smoke alarm back on the mounting plate, rotating it clockwise until it clicks into place. Finally, press the test button to confirm functionality.

The smoke alarm comes with a three-year limited warranty against manufacturing faults, valid from the date of purchase. Batteries are not covered. Warranty liability is limited to the value of a corresponding smoke alarm. Defective units should be returned to the dealer with a problem description. A receipt confirming the purchase date is required for warranty claims.

Maintenance and cleaning are essential for optimal performance. The smoke alarm should be cleaned regularly, at least twice a year. Vacuum the exterior along the opening to the optical chamber to remove dust or dirt. Do not attempt to open the hatch to clean the inside of the smoke alarm, as this will void the warranty.

The device is mainly made of recyclable materials. Packaging and device contents should not be disposed of with household waste but must be recycled according to EU Directive 2002/96/EC on waste from electrical and electronic equipment (WEEE). For more information on waste disposal, contact your dealer or local authority.

The Nexa Bridge and FS-558/RF smoke alarm can be integrated to create an automated system. This allows for functionalities such as sending notifications to your mobile phone, activating sirens, or switching on lights when the smoke alarm is triggered.

Nexa FS-558/RF Specifications

General IconGeneral
Power SourceBattery
Battery9V
ConnectivityRF
Radio Frequency433.92 MHz
Test ButtonYes
Operating Temperature0°C to +40°C
Sensor TypeOptical
Alarm Volume85 dB

Related product manuals