AHEAD OF THE FLOW
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
5
®
4. OPEN and SHUT Target Adjustment
4.1 All NIBCO Indicator Posts are shipped for use with “left-hand” (counter-clockwise) opening valves.
4.2 Remove 2 Nuts (4) and 2 T-Head Bolts (3) that secure Cap (2) to Indicator Post. See Fig. 2.
4.3 Grasp Cap (2) and remove from Indicator Post by lifting upward until Target assembly is clear.
4.4 Target Plates (8 & 9) must be positioned with the OPEN Plate (8) above the SHUT Plate (9) for “left-hand” (counter-clockwise)
opening valves. See Fig. 5.
TARGET ASSEMBLY PARTS LIST
NO. DESCRIPTION MATERIAL SPECIFICATION QTY.
7 LEADING BOGIE BRONZE ASTM B584 C84400 / B62 C83600 1
8 TARGET PLATE, OPEN ALUMINUM ASTM B26 2
9 TARGET PLATE, SHUT ALUMINUM ASTM B26 2
10 EXTENSION PLATE STEEL, PAINTED BLACK ASTM A1008 2
11 TARGET ROD BRASS ASTM B16 C36000 2
21 SCREW, SLOTTED FLAT HD. STAINLESS STEEL S30400 4
37 SCREW, SOCKET HD. SET STAINLESS STEEL S30400 6
Table 3
Fig. 5
NOTE: Only half of
assembly is shown

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibco NIP-2AW series and is the answer not in the manual?

Nibco NIP-2AW series Specifications

General IconGeneral
BrandNibco
ModelNIP-2AW series
CategoryControl Unit
LanguageEnglish

Related product manuals