FIGHTER 1320/1330 / F1330 prioritises loading of hot water
with half the output (heat pump module B) via a reversing
valve. When the hot water heater/accumulator tank is fully
charged, the reversing valve switches to the heating circuit.
When there is a heat demand, module A starts first. For larger
heating demands, module B is also started. FIGHTER
1320/1330 / F1330 connects ELK 15 in steps when the energy
requirement exceeds the heat pump capacity.
If HWH/ACC is fitted with an immersion heater and a junction
box the "Extra hot water" function can be used. A by-pass
contactor is recommended.
Menu settings
1.
Select “Electric” in menu 9.1.8 - "Additive".
2.
Select ”Binary” in menu 6.2.1 - "Immersionheater type".
3.
Select ”2” in menu 6.2.2 - "Immersionheatrelays".
4.
Select "1" in menu 6.2.3 - "Steps at 2h delay", if a re-
striction of the electrical power for 5 kW within 2 hours
from start-up is required.
5.
Select "Auto" operating mode in order for the electrical
addition to be permitted to start.
Check the max. output setting on knob (101), in FIGHTER
1320/1330 / F1330.
See the appropriate “Installation and Maintenance Instruc-
tions” for FIGHTER 1320/1330 / F1330 for more information.