Heating curve
Domestic hot water
Settings for hot water production have been set at the factory, but it may be necessary to adjust them to match the user´s needs.
> Domestic hot water
*If a weekday is chosen, the legionella function will start at 1:00 at night and heat the domestic hot water to 65 °C. The function will only
work if the supplemental electric heating is activated.
Max. temperature
Min. temperature
Supply air temperature
Outdoor temperature
> Supplemental electric heating
hot water
Settings:
Standard setting:
Description:
Off / 5 85 ºC
30 ºC
Off: The supplemental electric heating is de-activated by the
user.
5 - 85 ºC: Indicates below which temperature (T11) the supple-
mental electric heating should help with heating of the domes-
tic hot water.
> Hot water temperature Settings:
Standard setting:
Description:
Off / 5 60 ºC
45 ºC
Off: The hot water production is switched off by the user.
5 - 60 ºC: Indicates below which temperature (T12) the com-
pressor should produce hot water.
> Day for legionella treatment Settings:
Standard setting:
Description:
None / Mon / Tue / Wed / Thu / Fri / Sat / Sun
None
Here it is stated whether the unit should run a weekly legionella
treatment *.
> Legionella temperature Settings:
Standard setting:
Description:
50 70 ºC
65 ºC
The temperature of the legionella treatment