DW1500274
Rev.K3
Mar 6, 2017
Installation Instructions
Before Installation
Please read these instructions carefully and keep for future
reference.
The information in this document is subject to change without
notice. For updates please refer to our website.
・Do not use the products outside the rated power supply voltage
range specified in the Specifications. It may cause a fire or
damage to equipment.
・Do not disassemble, repair, or modify the products. It may cause
a fire or electric shock.
・Make sure to turn the power off before commencing any wiring
work. Otherwise it may cause electric shock or damage to
equipment.
・Do not use any tester other than the one specified for testing. It
may cause damage to equipment.
Note
・Follow the requirements for the installation of the products in
accordance with the Specifications. Otherwise it may cause
malfunction.
・The products should not be installed in the following places, as it
may cause damage to equipment:
- Place with plenty of air flow (close to a ventilation fan, air
conditioner, or place with drafts)
- Place close to heating appliance
- Place with a constantly high temperature or humidity
- Place with lots of dust or insects
- Place with exhaust gas such as garage
- Place where oil, dust, iron powder, chemicals, or hydrogen
sulphide may occur or affect the products
These instructions explain how to install and test UL Listed Nittan
detectors and bases.
For the details of each product, please refer to “Instruction Manual”
on the website: http://www.nittan.com
Table 1: UL Listed Product Instruction Manual
Install the detectors/bases in accordance with these instructions,
applicable NFPA standards, local codes, and the authorities
having jurisdiction. Failure to follow these instructions may result
in failure of detectors to initiate an alarm condition. Nittan is not
responsible for detectors and bases that have been improperly
installed, tested, or maintained.
Table 2: Electrical box for base
Applicable electrical box
EVA-STB-SCI
with
STBA-ADP
Connect wiring to the detectors/bases as shown in the Section2.
Detectors and bases may be mixed on the same initiating loop as
long as the number of two-wire powered detectors does not
exceed the specifications of the control panel. For the
specifications of detectors/bases, see Table 3.
NITTAN COMPANY, LIMITED
1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN
http://www.nittan.com