5 Parameter
BU 0600 en-2319 79
P002 Display factor S
Factory setting { 1 }
The selected operating value in parameter P001 "Display selection" is multiplied by
the scaling factor in P000 and displayed in the "Operating display".
It is therefore possible to display system-specific operating values e.g. throughput
quantity.
P003 Supervisor code
Factory setting { 1 }
The scope of the visible parameters can be influenced by setting the supervisor code.
If parameterisation is carried out with the NORDCON software, the settings 2 ... 9999
the settings are as for the 0 setting.
Setting values
Value Meaning
0 Supervisor mode Off
The supervisor parameters are not visible.
1 Supervisor mode On
All parameters are visible.
The supervisor parameters are not visible.
P004 Password S
Setting range - 32768 … 32767
Entry of the password from P005 to unlock all visible, editable parameters.
The value which is entered here is lost when the control board / the frequency inverter
is switched off. Password protection is active again.
P005 Change password S
Factory setting { 0 }
Specification of a password to protect the setting values of editable parameters from
unauthorised changes. Password protection can be temporarily suspended via P004.
The password is generally cancelled with setting "0" in P005.