8 Additional Information
BU 0200 GB Subject to technical alterations 169
Device type
Max. motor cable, shielded
Jumper position
See Section
2.6.4 - 2.6.6
Cable emissions 150kHz - 30 MHz
Class A 1 C2 Class B 1 C1
SK 2x5E, motor-mounted
2 - 1
2 - 2
SK 2x5E wall-mounted
2 - 1
2 - 2
Overview of the standards, which according to product standard EN 61800-3 are applicable as testing and
measuring methods for electric drives whose speed can be altered:
Interference emission
Emission from cables
(interference voltage)
EN 55011
A 1 or C2
-
Radiated emissions
(Interference field strength)
EN 55011
A 1 or C2
-
Interference immunity EN 61000-6-1, EN 61000-6-2
ESD, discharge of static electricity EN 61000-4-2 6kV (CD), 8kV (AD)
EMF, high frequency electro-magnetic fields EN 61000-4-3 10V/m; 80 - 1000MHz
Burst on control cables EN 61000-4-4 1kV
Burst on mains and motor cables EN 61000-4-4 2kV
Surge (phase-phase / phase-ground) EN 61000-4-5 1kV / 2kV
Cable-led interference due to
high frequency fields
EN 61000-4-6 10V, 0.15 - 80MHz
Voltage fluctuations and drops EN 61000-2-1 +10%, -15%; 90%
Voltage asymmetries and frequency
changes
EN 61000-2-4 3%; 2%
Wiring recommendations for mounting near to motor
M
3 ~
PE
L
1