13
Table 7. Charging Table for T4BE-060KA Series (5 Ton Models) – Restrictor Matches
SUCT.
PRESS.
OUTDOOR TEMPERATURE (°F)
70 75 80 85 90 95 100 105
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
LIQ.
PRESS.
DIS.
TEMP.
121 244 135
123
245 135
267 141
125 246 135
268 141
290 147
127
247 136
269 142
291 147
313 154
129 248 136
270 142
292 148
314 154
336 160
131 271 142
293 148
315 154
337 160
359 166
133 295 148
317 154
338 160
360 166
382 172
135 318 154
340 160
362 166
383 172
405 178
137 319 154 341 160
363 166
385 172
406 178
139 342 160 364 166
386 172
408 178
141 365 166
387 172
409 178
143 388 172 410 178
145 411 178
147